DS7060-AUS Reference Guide Copyright 2001 Detection Systems, Inc. Page 11
6.9 Address 09 - User Control
Duress Code: If this option is selected and Code 14 is
used to disarm the system, a duress report will be sent
as the system is otherwise disarmed normally. User
Code 14 will not arm the system, or report duress, if the
system is not armed.
Guest Code: If this option is selected, Code 15 is a
guest code. It can be enabled by pressing [PIN] [#] [8]
[4]. It will remain active until the panel is disarmed with
any other valid code.
Arming Warning: If this option is selected, the alarm
output will turn on for 2 seconds when the panel is
armed.
Keypad Audible During Exit Delay: Selection of this
option will cause the keypad sounders to beep during
the exit delay time. A one second beep will sound at 5
second intervals, changing to a 3-beep tone at 10 and 5
seconds prior to the end of the delay.
Keyswitch Arming Warning: Selecting this option will
activate any output programmed as Intrusion, Follow
Burg Alarm, or Follow Burg Alarm and Fire Alarm. The
output will beep once (200 ms ON) when a keyswitch
toggle zone arms the system. A double beep will occur
(200 ms ON-OFF-ON) when a keyswitch toggle zone
disarms the system.
6.10 Address 10 - General Control
Siren on Comm. Fail for Silent Zone: If programmed,
a silent zone will sound the alarm outputs if the zone is
in an alarm condition and the system fails to
communicate with the central station.
Closing Ringback: If programmed, the keypad
sounders and Output 3 will activate for 2 seconds after
the system is armed and the closing report is
successfully sent. This requires Closing Ringback and
Closing Report to be programmed. If the panel does not
report to a central station, use “Arming Warning” in
Address 9.
Swinger Shunt: If enabled, a zone can only alarm or
trouble up to three times per armed period. After the
third alarm or trouble, the zone will be bypassed and a
bypass report for this zone will be sent. Fire zones are
never swinger shunted.
50 Hz/60 Hz: Set to local power type. The panel clock
is synchronized to the power line frequency. 60 Hz
required for UL Listed Requirements.
Keypad Mode: Commercial Mode requires a PIN
number for all functions. Residential Mode only requires
a PIN number for disarming and silencing alarms.
Quick Arm: If enabled, a PIN is not needed to arm.
NOTE: Used only in conjunction with commercial
mode.