DS7240-UK Control/Communicator Reference Guide
Aux
Pwr
+
Note 1
: Jumper J2-PO1 must be in place for connection
to NAC or other powered alarm device.
Installer Switch
L-3 Com L-4 L-5 Com L-6 L-7 Com L-8PO3 PO2
Alrm
+
A B
SMK
+
Com L-2PO4
PO1
L-1
Installer
Keypad
Lock
Installer
Switch
Green
Yellow
Red
Black
A B C D
P
S
Keypads, Expanders
Printer modules &
Communication modules
(up to 19 total devices)
P
S
P
S
P
S
Data
Data
Auxilliary Powered Devices 11.5 to 12.4 VDC.
With 7.0 Ah battery,120 mA for 24 hrs for Fire and
Combined Fire/Burglary. 600 mA for other.
Include keypads in calculations.
POWER SUPPLY REQUIREMENTS
The Power Supply provides a maximum of 600 mA for the Control Panel and All Accessory Devices.
Requirements for battery standby time may reduce allowable output.
CAUTION
: See Installers Guide for power requirements relating to terminals [Alrm+] and [+Aux].
Outputs PO3 & PO4 can sink up
to 500 mA 12 VDC.
JP2
Supervised with 2k2
EOL Resistors
(P/N:47819).
Typical Initiating Devices
are Door Contacts NO/NC,
Floor Mats, Motion
Sensors, Glass Break
Detectors, etc.
A
B1
B
A1
A
B1
B
A1
Incoming
Phone
Line
Premises
Phone
PO1 Terminals can be configured as an alarm power output.
JP2- PO1 Jumper must be closed.
Orange
Yellow
Green/Yellow
Blue
Brown
R
Y
G
B
Rated Voltage: 230 V
Rated Frequency: 50 Hz
Rated Input Current: 250 mA max.
For PERMANENTLY CONNECTED
EQUIPMENT, a readily accessible
disconnect device shall be incorporated
into the building installation wiring.
CAUTION
RISK OF EXPLOSION IF
BATTERY IS REPLACED BY AN
INCORRECT TYPE.
DISPOSE OF USED BATTERIES
ACCORDING TO THE
INSTRUCTIONS
Maximum charging
current is 1.1 A.
Replace Battery every 3 to 5 yrs.
with a lead acid battery such as
P/N:440054
(12 V, 7 Amp-Hr, 6 cells)
Battery Capacity
:
Min 5.0 Ah Max 18.0 Ah
Recommended Battery
Manufacturers
:
POWER SONIC:
PS-1270,
PS-12180
YUASA:
NP7-12,
NPG18-12
Green/Yellow
For continued protection against risk
of fire, replace only with same type and
rating of fuse.
Fuse Rating: 0.25 A, 250 V Slow Blow
Tamper Zones
Output PO2 can be used with
Alarm+ as a supervised siren driver.
Connect an approved 4 or 8
siren.
Alternatively, PO2 can sink up to 500 mA 12 VDC.
Wall and Lid
Tamper
Switches
NEG TRIG
+12 V
STRB NEG
Bell
0 V
Tamp 0 V
Supervised Zones
Open 10.4 to 14.0 VDC
Fault 8.3 to 9.4 VDC
Normal 6.4 to 7.4 VDC
Short 0.0 to 5.7 VDC
All Resistors
2k2
(P/N:47819)
Figure 1: Panel Wiring Connections
See Table 1 on page 2 for terminal descriptions.

Table of Contents

Questions and Answers

  • B
    Barry JenkinsAug 12, 2025
    What to do if a Keyswitch zone trouble won't clear on my Bosch DS7240-UK?
    • K
      Kristina RayAug 12, 2025
      If a Keyswitch zone trouble on your Bosch Cell Phone doesn't clear even when the zone returns to normal, it might be due to Swinger Shunt not being enabled on the Zone Function. To resolve this, arm and then disarm the panel to clear the current trouble. To prevent this from happening again, verify the Keyswitch Zone Function programming and ensure that the Swinger Shunt feature is disabled.
  • J
    jphillipsAug 19, 2025
    What to do if I cannot clear a tamper trouble on my Bosch DS7240-UK?
    • S
      Shawn GarciaAug 19, 2025
      If you have a tamper trouble on a zone of your Bosch Cell Phone that you can't clear by entering the Installer PIN and then pressing the [System Reset] key, the zone might be bypassed. To fix this, press the [Bypass] key to manually unbypass the zone. Then, enter the Installer’s PIN, and press the [System Reset] key.
  • J
    joshua89Aug 27, 2025
    Why does my Bosch DS7240-UK not arm when I enter a valid PIN?
    • P
      Phillip FisherAug 27, 2025
      If you enter a valid PIN to arm an Area on your Bosch Cell Phone, but the Area doesn't arm, it could be due to a couple of reasons. First, ensure that at least one zone is programmed for each Area. Second, verify that the user attempting to arm the system has the appropriate Authority Level.
  • S
    Sarah CarrilloSep 4, 2025
    Why does my Bosch DS7240-UK Cell Phone keep switching to Perimeter Only after arming All On?
    • E
      Erin HolmesSep 4, 2025
      If your Bosch Cell Phone panel keeps changing to Perimeter Only after you've armed it All On, it's likely because the “All On-No Exit” arming option is enabled. This means that when the panel was armed, no one triggered an Exit Delay zone, so the panel didn't arm those internal zones.

Bosch DS7240-UK Specifications

General IconGeneral
BrandBosch
ModelDS7240-UK
CategoryCell Phone
LanguageEnglish

Related product manuals