Page 52 P/N: 4998122677Cr1 Copyright 2003 Bosch Security Systems DS7240-UK Reference Guide
PART III: PANEL PROGRAMMING
26.8 Automatic Test [137] Report Interval
• Address: 0254
• Default: 3 (7 Days)
• Selections:
• 0 = No Automatic Test
• 1 = 1 Hour
• 2 = 1 Day
• 3 = 7 Days
• 4 = 28 Days
26.8.1 Parameter Description
Entering zero (0) at this parameter disables the Automatic Test [137] report feature.
The one-hour interval is incremented on the minute. For example, if you set the Automatic Test Time parameter to 1020 (10:20
am), the Automatic Test Interval is one hour, and left programming mode at 11:10, then the panel would send a test report at
11:20 am (less than one hour after leaving programming mode). The next test report would come at 12:20 pm.
The one-day, seven-day and 28-day intervals are incremented at midnight (2400). For example, if you set the Automatic Test
Time parameter to 1020 (10:20 am), the Automatic Test Interval is one day and left programming mode at 10:10 am, then the
panel would not send a test report until 10:20 the next day (after the one-day interval increment at midnight).
If the Automatic Test report is disabled in Section 26.6 Automatic Test [137] Report Options (page 51), this parameter
becomes meaningless for the Automatic Test.
26.9 Test Report Routing
• Address: 0255
• Default: See table below
• Selections: 0-5
Data Digit Entry Option
0 No Reports, no Events to Log/Printer
Default 1 Reports to Destination 1, Events to Log/Printer
2 Reports to Destination 2, Events to Log/Printer
3 Reports to Destinations 1 & 2, Events to Log/Printer
4 Reports to Destination 2 only on Destination 1 Comm Fail Event, Events to Log/Printer
5 No reports, Events to Log/Printer
26.9.1 Parameter Description
This is a global (affects all areas) parameter.
Test reports include the System Test [137] [138] reports. The Walk Test Start [158] and Walk Test End [159] reports follow
their own routing.
Reporting must be enabled at the Global Reporting Options parameter (page 38) and at least one phone number
must be entered for one routing destination (page 32).