Page 86 P/N: 4998122677Cr1 Copyright 2003 Bosch Security Systems DS7240-UK Reference Guide
PART III: PANEL PROGRAMMING
35.0 Locations
The DS7240-UK supports up to 40 Locations. Locations are configured through the following parameters: Device, Zone
Function, Area and Zone Number. All four of these parameters must be configured for each Location being used in the
system.
See Table 20 for Location parameter addresses and defaults (defaults are shown like this).
Location Parameters
These columns show the default Address
programming for each of the four Location
parameters. These parameters configure each
Location.
Device Parameter Selections
These columns show the selections for the “Device” parameter. The Device
parameter tells the panel where to find the sensor loop (or transmitter) status for
each Location.
Location
#
Device Zone
Function
Area Zone # On-board
(1)
DX2010
(2)
DX2010
Doubled
(3)
RF Rcvr 1
(4)
RF Rcvr 2
(5)
1 Adr 0706
(1)
Adr 0707
(11)
Adr 0708
(1)
Adr 0709-0710
(0-1)
3.65 k Ω only
when doubled
w/ 9
DBus Adr
101 Loop 1
DBus Adr 50
Xmitter 1
DBus Adr 51
Xmitter 1
2
Adr 0711
(1)
Adr 0712
(13)
Adr 0713
(1)
Adr 0714-0715
(0-2)
3.65 k Ω only
when doubled
w/ 10
DBus Adr
101 Loop 2
DBus Adr 50
Xmitter 2
DBus Adr 51
Xmitter 2
3
Adr 0716
(1)
Adr 0717
(14)
Adr 0718
(1)
Adr 0719-0720
(0-3)
3.65 k Ω only
when doubled
w/ 11
DBus Adr
101 Loop 3
DBus Adr 50
Xmitter 3
DBus Adr 51
Xmitter 3
4 Adr 0721
(1)
Adr 0722
(14)
Adr 0723
(1)
Adr 0724-0725
(0-4)
3.65 k Ω only
when doubled
w/ 12
DBus Adr
101 Loop 4
DBus Adr 50
Xmitter 4
DBus Adr 51
Xmitter 4
5 Adr 0726
(1)
Adr 0727
(15)
Adr 0728
(1)
Adr 0729-0730
(0-5)
3.65 k Ω only
when doubled
w/ 13
DBus Adr
101 Loop 5
DBus Adr 50
Xmitter 5
DBus Adr 51
Xmitter 5
6 Adr 0731
(1)
Adr 0732
(15)
Adr 0733
(1)
Adr 0734-0735
(0-6)
3.65 k Ω only
when doubled
w/ 14
DBus Adr
101 Loop 6
DBus Adr 50
Xmitter 6
DBus Adr 51
Xmitter 6
7 Adr 0736
(1)
Adr 0737
(4)
Adr 0738
(1)
Adr 0739-0740
(0-7)
3.65 k Ω only
when doubled
w/ 15
DBus Adr
101 Loop 7
DBus Adr 50
Xmitter 7
DBus Adr 51
Xmitter 7
8 Adr 0741
(1)
Adr 0742
(4)
Adr 0743
(1)
Adr 0744-0745
(0-8)
3.65 k Ω only
when doubled
w/ 16
DBus Adr
101 Loop 8
DBus Adr 50
Xmitter 8
DBus Adr 51
Xmitter 8
9 Adr 0746
(0)
Adr 0747
(14)
Adr 0748
(1)
Adr 0749-0750
(0-9)
Doubled w/ 1
2.2 k Ω
DBus Adr
102 Loop 1
DBus Adr 106
Loop 1; 3.65 kΩ
DBus Adr 50
Xmitter 9
DBus Adr 51
Xmitter 9
10 Adr 0751
(0)
Adr 0752
(14)
Adr 0753
(1)
Adr 0754-0755
(1-0)
Doubled w/ 2
2.2 k Ω
DBus Adr
102 Loop 2
DBus Adr 106
Loop 2; 3.65 kΩ
DBus Adr 50
Xmitter 10
DBus Adr 51
Xmitter 10
11
Adr 0756
(0)
Adr 0757
(14)
Adr 0758
(1)
Adr 0759-0760
(1-1)
Doubled w/ 3
2.2 k Ω
DBus Adr
102 Loop 3
DBus Adr 106
Loop 3; 3.65 kΩ
DBus Adr 50
Xmitter 11
DBus Adr 51
Xmitter 11
12 Adr 0761
(0)
Adr 0762
(14)
Adr 0763
(1)
Adr 0764-0765
(1-2)
Doubled w/ 4
2.2 k Ω
DBus Adr
102 Loop 4
DBus Adr 106
Loop 4; 3.65 kΩ
DBus Adr 50
Xmitter 12
DBus Adr 51
Xmitter 12
13 Adr 0766
(0)
Adr 0767
(14)
Adr 0768
(1)
Adr 0769-0770
(1-3)
Doubled w/ 5
2.2 k Ω
DBus Adr
102 Loop 5
DBus Adr 106
Loop 5; 3.65 kΩ
DBus Adr 50
Xmitter 13
DBus Adr 51
Xmitter 13
14 Adr 0771
(0)
Adr 0772
(14)
Adr 0773
(1)
Adr 0774-0775
(1-4)
Doubled w/ 6
2.2 k Ω
DBus Adr
102 Loop 6
DBus Adr 106
Loop 6; 3.65 kΩ
DBus Adr 50
Xmitter 14
DBus Adr 51
Xmitter 14
15 Adr 0776
(0)
Adr 0777
(14)
Adr 0778
(1)
Adr 0779-0780
(1-5)
Doubled w/ 7
2.2 k Ω
DBus Adr
102 Loop 7
DBus Adr 106
Loop 7; 3.65 kΩ
DBus Adr 50
Xmitter 15
DBus Adr 51
Xmitter 15
16 Adr 0781
(0)
Adr 0782
(14)
Adr 0783
(1)
Adr 0784-0785
(1-6)
Doubled w/ 8
2.2 k Ω
DBus Adr
102 Loop 8
DBus Adr 106
Loop 8; 3.65 kΩ
DBus Adr 50
Xmitter 16
DBus Adr 51
Xmitter 16
Table 20: Location Configuration Parameters
* DBus = Data Bus; ** Xmitter = Transmitter
Zone doubling requires 3.65 k ΩΩ and 2.2 k ΩΩ EOL resistors as shown in Table 20. If zone doubling is not used, see
Section 37.1 On-board Location EOL Resistor Value on page 102 for on-board zone EOL configuration and
Section 41.8 DX2010 Configuration Options on page 123 for off-board zone EOL configuration.
See Section 43.0 Text Entry Parameters on page 125 for instructions on programming Location text.