DS7240-UK Reference Guide Copyright 2003 Bosch Security Systems P/N: 4998122677Cr1 Page 63
PART III: PANEL PROGRAMMING
29.2 Area # Opening [89-96]/Closing [42-67] Reporting Options
• Address:
• Area 1: 0296
• Area 2: 0318
• Area 3: 0340
• Area 4: 0362
• Default: See table below
• Selections: 0, 1, 3, 5, 7, 9, 11, 13, 15
Enter This Data Digit to Select Options
Area # Open/Close Reporting Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Open or Close Reports for Area #
••
Open/Close Reports (for All On) for Area # Enabled
•• •• •• •• •• •• •• ••
Restrict Open/Close Reports; Open afterAlarm, Close on
Force Arm
•• •• •• ••
Open/Close Reports for Perimeter Only (and Partial On)
Mode – Must also select Open/Close Reports (for All On)
•• •• •• ••
1 Second Bell Test on Closing Rpt Acknowledgement
•• •• •• ••
Default
29.2.1 Parameter Options
• Open/Close Reports for Area # Enabled: This parameter configures Opening/Closing reports for each area. This also
includes the report for the Extend Auto event (Event 21) (see Section 60.0 Panel Events and Reporting Formats on page
151). Opening [89-96] and Closing [42-67] reports must be enabled at the system level. Opening and Closing reports are
also enabled by Authority Level. Reporting must also be enabled at the system level (see Section 25.1 Global Reporting
Options on page 38).
• Restrict Open/Close Reports; Open From Alarm, Close on Force Arm: When selected and Bell Time has expired, the
panel only sends opening reports when the user disarms the system after an alarm. The panel only sends closing reports
when a zone is force-armed. Force arming is set by authority level and by Zone Function configuration.
Enabling the “Restrict Open/Close Reports” feature overrides the “First Area to Open/Last Area to Close
Reporting” feature. See Section 28.2 Arming Options 2 on page 56 for more information regarding the “First Area
to Open/Last Area to Close Reporting” feature.
• Open/Close Reports for Perimeter Only Mode: When selected, the panel sends closing reports when users arm the
system Perimeter Only. If any zones are bypassed, bypass reports are also sent. The panel sends opening reports when
users disarm the system. Perimeter Only arming is set by authority level and by Zone Function configuration.
• 1 Second Bell Test on Closing Ack: Outputs assigned to Alarm Output Functions 1-8, 1-9 and 1-10 activate for one
second. See Section 39.2 Function, Output ## on page 112 for output function descriptions.