18 en | Technical specifications Aspiration smoke detector LSN improved
2020.04 | 6.1 | F.01U.029.275 Operation guide Bosch Sicherheitssysteme GmbH
3.5.7 Device Mounting
1
2
FAS
-420 series
FAS-42 0
series
Mounting for FAS-420 series Aspirating Smoke Detector
1 Horizontal installation
2 Vertical installation
The MT-1 unit mounting is used if a direct wall installation is not possible, e.g. installation on
racks.
3.5.8 Measures for reducing operating noise
Absorption of the operating noises caused by airflows
1 Smoke aspiration pipe
2 Flexible hose
3 Fitting
4 Vibration absorbers
Vibration absorbers
The fans of the aspirating smoke detectors cause a noise level of approx.45dB(A). Mounting
the FAS-420 onto vibration absorbers can effectively reduce noise transmission through the
installation elements. This results in a reduction in the noise level from 1to 2dB(A).
Additional operating noises may be caused by vibrations on the pipe system, which are
generated by the air flowing through it. This can be remedied by inserting a corrugated hose
(approx.15cm long) between pipe system and aspirating smoke detector to create a flexible
transition.
In noise-sensitive areas, the sound level can also be reduced by installing a piece of plastic
pipe approximately 100mm long into the air outlet opening of the unit. This is done by
breaking out the pre-punched opening in the protective grille (e.g. using a small edge cutter).
All ‑SL variants are equipped with an extremely quiet fan that limits the noise level to
31dB(A). Thanks to the additional sound damper, fan noise can be reduced to 23dB(A); this
ensures that the detector is in accordance with DIN4109 for living and sleeping areas.