54 en | Planning Aspiration smoke detector LSN improved
2020.04 | 6.1 | F.01U.029.275 Operation guide Bosch Sicherheitssysteme GmbH
I-pipe system Number of air sampling openings
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Ø of all air sampling openings
in mm
a
6.0 5.0 4.4 4.0 3.6 3.4 3.2 3.0 3.0 3.0 3.0 2.5 2.5 2.5 2.5 2.5 2.5
a
Punch diameter of the aspiration reducing film sheet
U-pipe system - simplified planning
1 pipe system
FAS-420-TP1
FAS-420-TT1
2 pipe systems
FAS-420-TP2
FAS-420-TT2
FAS / FCS
FAS / FCS
d
d
i
12
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
i
1
2
3
4
5
6
7
8
9
10
U-pipe system, e.g. for equipment protection
Limiting values Min. distance FAS-420 – T-fitting 2m
U-pipe system Max. distance FAS-420 – T-fitting 20m
Max. branch length 20m
Max. overall pipe length (Ø 25mm) 60m
Min. distance between air sampling openings (d) 0.1m
Max. distance between air sampling openings (d) 4m
Max. number of air sampling openings (n) per pipe system 18
U-pipe system Number of air sampling openings
2 4 6 8 10 12 14 16 18
Ø of all air sampling openings in
mm
a
6.0 4.4 3.6 3.2 3.0 3.0 2.5 2.5 2.5
a
Punch diameter of the aspiration reducing film sheet