Operating Instructions
Greentherm T9800 SEO 160/199 | SECO 199 – 6 720 817 281 (2018/12)
30
OD (Operation Data)
Allows you to view various parameters of the current operation
of the appliance.
Press buttons or to choose the following
information:
0d (Chamber NTC) - current water temperature at heat
exchanger outlet.
1d (Inlet NTC) - current temperature of the temperature
sensor of the water inlet tube.
2d (Outlet NTC) - current temperature of the temperature
sensor of the water outlet pipe.
3d (Flow) - total flow, through main valve + bypass.
4d (barometric pressure) - current barometric pressure at
installation location.
5d (Fan Speed) - current fan speed.
6d (Output Power) - % current power.
7d (SS Hex NTC) - Flue gases temperature sensor at the
condensing unit inlet (between heat exchangers).
8d (Exhaust Gas NTC) - Exhaust flue gases temperature
sensor.
9d (Ambient NTC) - current temperature inside cabinet
near the fan.
10d (External Tank) - current temperature on the external
tank.
11d (Operation Cycles) - number of times burner has
been started. The number of cycles should be read from 4C
to 0C.
12d (Operation Hours) - number of minutes burner has
been started. Time should be read from 4H to 0H.
E - Exit.
How to select desired information:
Press the button to view the selected parameter.
The information is showed on the display.
Press the button to return to parameters list.
Press buttons or to select E.
Press the button to exit.
Numbers of cycles
To see how many cycles the appliance has done, please enter
the menu 11d (Operation Cycles).
After checking the sub-modes 0C, 1C, 2C, 3C, 4C, introduce
the values in a table as the example below;
Table 13 Total of cycles
In this example, the numbers of cycles is: 4061776.
In the calculation of number of cycles,
1 cycle means 1 ignition.
Numbers of hours
To see how many hours the appliance has worked, please enter
the menu 12d (Operation Hours).
After checking the sub-modes 0H, 1H, 2H, 3H, 4H, introduce
the values in a table as the example below;
Table 14 Total of hours
In this example, the numbers of hours is: 1863.
FH (Failure History)
Allows you to view the last 10 error codes.
Press buttons or to choose from 1F (most recent
failure) to 10F (older failure).
Press the button to view the selected failure.
The error code is showed on the display.
Press the button to return to failure list.
Press buttons or to select E.
Press the button to exit.
6.5.2 P9 (Purge)
Fig. 32 P9 - Purge
This menu allows you to purge the exhaust circuit.
Access to information / adjustments menu.
Display shows P4 (Information).
Press the button until the display shows P9 (Purge).
After 2 sec. the fan starts working to purge the exhaust
circuit.
4C 3C 2C 1C 0C
00 04 06 17 76
4H 3H 2H 1H 0H
00 00 00 18 63