Troubleshooting
Greentherm T9800 SEO 160/199 | SECO 199 – 6 720 817 281 (2018/12)
42
8.11.3 Factory default settings
To restore factory values for combustion settings.
Proceed with the following steps.
Restore factory values for P1 Max. Power
Access to menu P1 Max. Power.
Press symbols or to select rP Reset Parameters.
Press the symbol to select rE.
Press for 3 seconds.
Press the symbol .
The display blinks to confirm change.
Press the symbol .
The factory default values for P1 are restored.
Restore factory values for P2 Low Power
Access to menu P2 Low Power.
Press symbols or to select rP Reset Parameters.
Press the symbol to select rE.
Press for 3 seconds.
Press the symbol .
The display blinks to confirm change.
Press the symbol .
The factory default values for P2 are restored.
8.12 CO emissions check
In case air/gas combustion adjustment has been performed
check emissions using reference values in tables 18 and 19.
8.12.1 Access to CO
2
measuring port
WARNING:
Only a qualified technician can perform these steps.
This can cause carbon monoxide poisoning.
Follow the instructions carefully.
Allow the appliance to stabilize before performing CO
readings.
Let appliance warm up and wait for 5 minutes for each CO
readings.
This will avoid wrong CO readings.
Open a hot water tap and let the appliance work for 2 or 5
minutes.
Remove the protection from the front cover, see fig. 44.
Fig. 44 Remove protection
Remove the front cover from the appliance.
Enter in P1 and P2 menus to make the readings.
Place the front cover during the readings.
Insert analyzer probe into the measuring port (approx. 1.5"
inserted), see fig. 45.
Fig. 45 Measuring port