Troubleshooting
41
Greentherm T9800 SEO 160/199 | SECO 199 – 6 720 817 281 (2018/12)
Press the buttons or to adjust parameter value if
power bar level is out of range.
1)
Fig. 42 Gas adjust - L1 parameter
Press the button for 3 seconds to appliance assume
value.
Press the button to save the value.
Display will be back to P1 menu.
Press the button to enter L1 and verify if power bar
level is at middle point, see fig. 42.
Repeat the process until L1 gas adjust is correct.
Press button to finish the L1 gas adjust.
Press the button or until the display shows "A1".
Press the button to enter A1.
Display shows A1 value.
Verify if power by level is at middle point, see fig. 41.
Press the buttons or to adjust parameter value if
power bar level is out of range.
2)
Fig. 43 Air adjust - A1 parameter
Press the button for 3 seconds to appliance assume
value.
The value flashes as a sign of confirmation.
Press the button to finish the A1 air adjust.
Press the button or until the display shows "b1".
If b1 is blinking on the display,
Wait until it stops.
Press the button to enter b1.
Display shows the parameter value blinking during
calibration.
Wait until display shows b1 value blinking as a sign of
calibration complete.
Press button to finish the b1 automatic air adjust.
Press the button or until the display shows E.
Press the button .
Display shows P1.
Second step - Adjust the Low power (P2)
Keep hot water taps opened to adjust Low power (P2). The unit
will ramp down to low fire and the water flow should decrease
automatically.
Press the buttons or to select P2 (Low Power)
menu.
Press to enter P2 adjustment.
Display shows E.
Press or until L2 appears.
Press the button to enter L2.
Display shows L2 value.
Verify if power bar level is at middle point, see fig. 41.
Press the buttons or to adjust parameter value if
power bar level is out of range.
3)
Press the button for 3 seconds to appliance assume
value.
The value flashes as a sign of confirmation.
Press button to finish the L2 gas adjust (U1).
Parameter D2
Only a qualified technician can change this parameter.
Gas and Air adjustment is complete.
1) Increasing L1 value will cause an increase in power bar level
and vice-versa.
2) Increasing A1 value will cause a decrease in power bar level
and vice-versa.
3) Increasing L2 value will cause an increase in power bar level
and vice-versa.