Troubleshooting
43
Greentherm T9800 SEO 160/199 | SECO 199 – 6 720 817 281 (2018/12)
8.12.2 CO
2
and CO values
Table 18 CO & CO target numbers
Table 19 CO & CO target numbers
8.12.3 Returning to Service
Remove the analyzer probe and place the protection on the
front cover.
Remove the front cover to access HMI.
Press the button or until the display shows E.
Press the button to return main menu.
Display shows selected setpoint temperature.
Place the front cover.
CO
2
range (%) Max. CO level
(measured)
Greentherm T9800 SEO
199 000 BTU
Nat. Gas
max. input P1 8.4 % - 9.0 % < 250 ppm
min. input P2 N/A < 100 ppm
* Values above are for climate controlled conditions.
Inputs such as gas pressure, heating value of the gas,
humidity and temperature of combustion air all impact CO
and CO
2
values. Changes in these inputs can result in
different CO and CO
2
values on the same appliance.
CO
2
range (%) Max. CO level
(measured)
Greentherm T9800 SE O
160 000 BTU
Nat. Gas
max. input P1 8.5 % - 9.1 % < 250 ppm
min. input P2 N/A < 100 ppm
* Values above are for climate controlled conditions.
Inputs such as gas pressure, heating value of the gas,
humidity and temperature of combustion air all impact CO
and CO
2
values. Changes in these inputs can result in
different CO and CO
2
values on the same appliance.