6 Ambient conditions
Humidity 85% at 40°C (non-condensing)
Operating temperature 0 to 50 °C
Storage and transport temperature -20 to 70 °C
Shock protection IEC 60068-2-27
Overvoltage category 2
Contamination level 2, no condensation allowed
Mechanical strength IEC 60068-2-64, acceleration: 2G
Tab. 6-1: Ambient conditions
Defective product due to gases jeopardizing
functions
NOTICE
Due to the risk of corrosion, avoid sulphurous gases (e.g. sulphur dioxide (SO
2
)
and hydrogen suphide (H
2
S)). The product is not resistant against these gases.
Risk to damage the device due to external influ-
ences
NOTICE
Keep the device away from oils and emulsions.
Failure of the product due to contaminated air
NOTICE
The ambient air must not contain acids, alkaline solutions, corrosive agents,
salts, metal vapors and other electrically conductive contaminants in high
concentrations
The devices to be installed into the housing and installation compartments
must at least comply with the degree of protection IP 54 according to DIN EN
60529.
The device shall be provided in a suitable fire enclosure in the end-use appli-
cation.
7
Technical data
PR2100
CPU Intel Atom Single Core E3815
1.46 GHz
GPU Intel® HD Graphics
Memory Onboard 4G DDR3L, 1066 MHz RAM
6/29
Technical data
IndraControl PR21 Embedded Automa-
tion Computer
Bosch Rexroth AG R911389662_Edition 02