Panel Controller Maintenance – walktest | en 73
Bosch Sicherheitssysteme GmbH User Guide 2017.09 | 7.0 | F.01U.258.929
16 Maintenance – walktest
This chapter contains information about the following points:
Walktest groups, page 73
Starting and ending walktest, page 75
Ending walktest for all elements, page 75
Displaying tested or untested elements, page 76
Assigning tested elements to a walktest group, page 76
A walktest is indicated by a yellow LED display on the panel.
!
Caution!
Alarm or fault messages from detectors switched to walktest are not forwarded to
transmission devices or extinguishers.
Notice!
If a signaling device is activated during a walktest, it emits a different signal tone to the one it
emits in the alarm state.
16.1 Walktest groups
The following options are available for switching elements to walktest:
Select individual elements from lists and/or
Select previously defined walktest groups consisting of at least one element.
There are 12 pre-defined walktest groups. The number of possible walktest groups is
predefined: January to December.
Example:
Detectors which are to be tested in May, can be grouped together in a group called May.
New elements can be added to a group, and elements that have already been added can be
removed.
Notice!
Even if the elements in a group (e.g. January) have been completely deleted, this group will
still be displayed in the list.
16.1.1 Adding or deleting elements
In order to add elements to a walktest group or remove elements from it:
1. In the start menu, select Maintenance
2. Walktest
3. Create / Change walktest group
A list of the walktest groups is displayed.
4. Select a walktest group, e.g. February.
You can choose from a number of options:
Delete all: Delete all elements in the selected group.
Show / Change: Delete all elements in the selected walk test group and delete
individual elements.
Add: Display all elements that have not yet been assigned to a walk test group, and
add individual elements.
Cancel: Cancel the operation.