Error handling instructions for Split outdoor unit
Split ODU – 6 720 817 722 (2015/06)
11
2.5 Error code 23
2.5.1 Error diagnosis and countermeasure flow chart
Check Point
1. Check the WCN_P(L), P(N) connection condition ate the main PCB
(heater). Refer to wiring diagram.
2. Check the DC link voltage at no operation of compressor (280V).
3. Check the DC link voltage at operation of compressor (340V).
4. Check the DC link sensing signal (AHBW**6AO): 2.4~2.8V
(Graphic 12).
5. Check the DC link sensing signal (AHBW**8AO): 0.4~0.6V
(Graphic 13).
ODU Split 4, 6, 8
Fig. 11 ODU Split 4, 6, 8
Display
code
Title Cause of error
Check point & Normal
condition
23 DC link High
/ Low
voltage
• DC link
voltage is
above
420Vdc
• DC link
voltage is
below
140Vdc
1. Check CN_(L), CN_(N)
connection
2. Check input voltage
3. Check PCB DC link
voltage sensor parts
Table 9 Error code 23
Is input voltage normal? No -> 1. Check power input voltage
Yes
Is inverter PCB
assembly 1 power
connection normal?
No ->
1. Check power connection state
Yes
Is PCB (Inverter)
normal?
No -> 1. Replace PCB assembly 1
Yes
Recheck power and
installation condition
Table 10 Error diagnosis and countermeasure chart
IN/I
GND
Vdc
6 720 817 722-09.1I