Bosch Rexroth AG
Hydraulics
Zum Eisengießer 1
97816 Lohr am Main, Germany
Phone +49 (0) 93 52 / 18-0
Fax +49 (0) 93 52 / 18-23 58
documentation@boschrexroth.de
www.boschrexroth.de
© This document, as well as the data, specifications and other informa-
tion set forth in it, are the exclusive property of Bosch Rexroth AG. It
may not be reproduced or given to third parties without its consent.
The data specified above only serve to describe the product. No state-
ments concerning a certain condition or suitability for a certain applica-
tion can be derived from our information. The information given does not
release the user from the obligation of own judgment and verification. It
must be remembered that our products are subject to a natural process
of wear and aging.
10/10 Bosch Rexroth AG Hydraulics
Additional information RE 30110-Z/10.12
Commissioning
Step 1 Set the relevant jumper according to table 1.
Step 2 Set the clock frequency. Use a digital multimeter suitable for frequency measure-
ments in order to do so.
Connect the digital multimeter with the measuring sockets "I" and "M0" and using
the potentiometer f, set the frequency according to table 1.
Step 3: Set the step level.
Step 3.1: At the differential amplifier input, apply
+0.1 V at pin b14 and
connect pin b16 with 0 V.
Using the S+ potentiometer, set the step level according to table 1.
Step 3.2: Apply –0.1 V at pin b14 and
connect pin b16 with 0 V.
Using the S– potentiometer, set the step level according to table 1.
Step 4: Set the maximum current.
Step 4.1: Apply +10 V at pin b14 and
connect pin b16 with 0 V.
Using the Gw+ potentiometer, set the maximum current according to table 1.
Step 4.1: Apply –10 V at pin b14 and
connect pin b16 with 0 V.
Using the Gsw– potentiometer, set the maximum current according to table 1.
You must imperatively observe the additional information in
the operating instructions RE 30110-B before commissioning
the amplifier card.