No. Installer Setting Factory Setting Comments
(Notes follow this table) Default Options (More information follows this table)
7 1st Stage Fan Control HG FAN 1 HG FAN 1 Select for 1st stage Gas heating
[note 2] HE FAN 1 Select for 1st stage Electric heating
8 Emergency Heat] HE EMER HE EMER Select for Electric Emergency Heat
Fan Control [note 3] HG EMER Select for Gas Emergency Heat
9 Reversing Valve REVO REVO
Select for cool active Reversing Valve (O terminal)
(O/B Terminal) [note 4] REVB
Select for heat active Reversing Valve (B terminal)
10 Fossil Fuel AE AUX AE AUX
Select for Electric Auxiliary heat (with compressor)
Backup Heat [note 3] AG AUX
Select for Gas Auxiliary heat (without compressor)
11
C
ompressor Power Outage
oF CPOP oF CPOP Disables Power Outage Lockout Delay
Protection [notes 3, 5] on CPOP Enables Power Outage Lockout Delay
12 AC Power Interrupt
AC oF MONR
AC oF MONR Disables AC Power Interrupt Warning
Warning [note 5] AC on MONR Enables AC Power Interrupt Warning
13 Compressor Short 5 CSCP 5, 4, 3, 2 or Select a compressor short cycle protection delay
Cycle Protection [note 6] 0 CSCP of 5, 4, 3, 2 or 0 minutes
14 Residual Cooling 60 FAN 90, 60, 30 Select a Residual Cooling Fan Delay of 90, 60,
Fan Delay [note 6] or 0 FAN 30 or 0 seconds.
15 Circulating Fan Lock oF CIRC oF CIRC Disables Circulating Fan Lock mode
on CIRC Enables Circulating Fan Lock mode
16 Indoor Remote Sensor I SENS I SENS Temperature is sensed from thermostat only.
Control* [note 7] E SENS Temperature is sensed from remote sensor only.
A SENS Temperature is combined with the thermostat
and the remote sensor.
17 Lockout Security Level 2 LOCK 2 LOCK If locked – Complete lockout is enabled
1 LOCK If locked – Partial lockout is enabled (SpeedBar
®
is still functional)
18 Auto Changeover 3 BAND 2, 3, 4 or 5 Select a Dead Band of 2°, 3°, 4° or 5˚ F
Dead Band [note 8] BAND
(1.0°, 2.0° or 3.0° C) for Auto Changeover mode.
19 Compressor Balance NO BALC NO BALC Disables Balance Points
Point [notes 3, 9] 15-50 BALC Select a Compressor Balance Point of 15°- 50°F
(-9°-10° C)
20 Auxiliary Heat Balance NO BALA NO BALA Disables Balance Points
Point [notes 3, 9]
70-40 BALA
Select a Auxiliary Heat Balance Point of 70°- 40° F
(21°- 4.0° C)
21
Heat Set Point Upper Limit
90LIM 90-60 LIM
Select a Heat Set Point Upper Limit of 90°-60° F
(32°-10° C)
22
Cool Set Point Lower Limit
45LIM 45-80 LIM
Select a Cool Set Point Lower Limit of 45°-80° F
[note 6] (7.0°-27° C)
9 Installer Manual
*When a Braeburn
®
outdoor sensor is connected, the thermostat automatically recognizes it. Press BACK and NEXT at the
same time to display outdoor temperature.
NOTE: Additional options such as Service Monitors, Setting the lock code, etc. are located in the User
Settings – See User manual for information on setting these options.