100/150/200 Amp Automatic
Transfer Switch
with Service Disconnect and
AC Control Module™
Installation Manual
Questions?
Help is just a moment away!
Call: Transfer Switch Helpline
800-743-4115 Monday - Friday 8:00 AM - 5:00 PM Central Time
NOT
for
REPRODUCTION

Questions and Answers

  • T
    Thomas HebertJul 29, 2025
    What to do if my Briggs & Stratton 100 does not transfer to generator?
    • V
      vangianJul 29, 2025
      If your automatic transfer switch isn't transferring to the generator, here are a few things to check: * First, make sure the generator circuit breaker is not open. If it is, reset it. * Next, check the generator disconnect circuit breaker in the transfer switch and reset it if necessary. * If the generator voltage is not acceptable, refer to the generator manual.
  • J
    James EvansAug 6, 2025
    What to do if my Briggs & Stratton 100 Switch does not transfer to utility power?
    • D
      Dylan MorganAug 6, 2025
      If the automatic transfer switch fails to transfer to utility power, check the following: 1. Ensure the utility disconnect circuit breaker in the transfer switch is not open; reset it if needed. 2. If the utility voltage is unacceptable, wait for it to return to normal.
  • U
    ujohnsonAug 12, 2025
    Why is my Briggs & Stratton Switch generator still running after utility power is restored?
    • K
      kelly62Aug 13, 2025
      The generator might continue to run after utility power returns due to these reasons: * The minimum engine run time hasn't elapsed yet; wait five minutes for the transfer switch to retransfer to utility power. * A fuse in the transfer switch might be defective; inspect the fuses and replace them if needed.
  • R
    Renee AlvarezAug 20, 2025
    What to do if generator or supervised loads are operating improperly when generator is supplying power in Briggs & Stratton 100?
    • M
      Madison DixonAug 21, 2025
      If the generator or supervised loads are operating improperly when the generator is supplying power, consider the following: * Check the A-A or B-B contacts for proper operation and/or check control wiring to external load. * The generator might be overloaded; decrease the load to the generator. * Ensure the current transformer is connected by plugging the CT connectors into the control module. * If the current transformer is broken, contact your local authorized service center.

Summary

Important Safety Instructions

Safety Symbols and Meanings

Explains safety alert symbols, signal words, and their meanings for hazard awareness.

Hazard Warnings and Precautions

Details critical warnings regarding shock hazards, wiring, and chemical exposure.

Installation

Delivery Inspection

Power Wiring Interconnections

Supervisory Control Wiring

System Setup

Testing the Automatic Transfer Switch

Operational Phases

Details the sequence of operations during power transfer testing, including utility fail and retransfer.

Troubleshooting