EasyManuals Logo

Bryant 355BAV User Manual

Bryant 355BAV
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
39
lows:
Low--heat
--30 seconds after the gas valve GV--M is opened,
the BLWM is turned ON at low--heat airflow.
High--heat
--35 seconds after gas valve GV--M is opened, the
BLWM is turned ON at high--heat airflow.
Simultaneously, the humidifier terminal HUM and electron-
ic air cleaner terminal EAC--1 are energized and remain en-
ergized throughout the heating cycle.
7. Switching From Low-- To High-- Heat-- If the furnace
control CPU switches from low--heat to high--heat, the fur-
nace control CPU will de--energize the the high--heat pres-
sure switch relay HPSR to close the NC contact and slowly
increase the inducer motor speed until the high--heat pres-
sure switch HPS closes. When the high--heat pressure
switch HPS closes, the high--heat gas valve solenoid GV--
HI is energized and the inducer motor RPM is noted by the
furnace control CPU. The RPM is used to evaluate vent sys-
tem resistance. This evaluation is then used to determine the
required RPM necessary to operate the inducer motor in
high--heat mode. The blower motor BLWM will transition
to high--heat airflow five seconds after the furnace control
CPU switches from low--heat to high--heat.
8. Switching From High-- To Low-- Heat--The furnace con-
trol CPU will not switch from high--heat to low--heat while
the thermostat R--to--W circuit is closed when using a
single--stage thermostat.
9. Blower--Off delay-- When the thermostat is satisfied, the R
to W circuit is opened, de--energizing the gas valve GV--M,
stopping gas flow to the burners, and de--energizing the hu-
midifier terminal HUM. The inducer motor IDM will re-
main energized for a 15--second post--purge period. The
blower motor BLWM and air cleaner terminal EAC--1 will
remain energized at low--heat airflow or transition to low--
heat airflow for 90, 120, 150, or 180 seconds (depending on
selection at blower--OFF delay switches). The furnace con-
trol CPU is factory--set for a 120--second blower--OFF
delay.
TWO--STAGE THERMOSTAT AND TWO--STAGE
HEA
TING
See Fig. 49 for thermostat connections.
NOTE: In this mode, the low--heat only switch SW1--2 must be
ON to select the low--heat only operation mode in response to
closing the thermostat R--to--W1 circuit. Closing the thermostat
R--to--W1--and--W2 circuits always causes high--heat operation,
regardless of the setting of the low--heat--only switch.
The wall thermostat “calls for heat,” closing the R toW1 circuit for
low--heat or closing the R to W1--and--W2 circuits for high--heat.
The furnace control performs a self--check and verifies the low heat
and high--heat pressure switch contacts LPS and HPS are open.
The start--up and shutdown functions and delays described in item
1. above apply to 2--stage heating mode as well, except for
switching from low-- to high--heat and vice versa.
1. Switching From Low-- To High-- Heat--If the thermostat R
to W1 circuit is closed and the R to W2 circuit closes, the
furnace control CPU will de--energize the high--heat pres-
sure switch relay HPSR to close the NC contact and slowly
increase the inducer motor speed until the high--heat pres-
sure switch HPS closes. When the high--heat pressure
switch closes, the high--heat gas valve solenoid GV--HI is
energized and the inducer motor RPM is noted by the fur-
nace control CPU. The RPM is used to evaluate vent system
resistance. This evaluation is then used to determine the re-
quired RPM necessary to operate the inducer motor in
high--heat mode. The blower motor BLWM will transition
to high--heat airflow five seconds after the R to W2 circuit
closes.
2. Switching From High-- To Low-- Heat-- If the thermostat
R to W2 circuit opens, and the R to W1 circuit remains
closed, the furnace control CPU will energize the high--heat
pressure switch relay HPSR to open the NC contact and
slowly decrease the inducer motor speed to the required
low--heat RPM. When the high--heat pressure switch HPS
opens, the high--heat gas valve solenoid GV--HI is de--ener-
gized. When the inducer motor IDM reduces pressure suffi-
ciently, the high--heat pressure switch HPS will open. The
gas valve solenoid GV--M will remain energized as long as
the low--heat pressure switch LPS remains closed. The
blower motor BLWM will transition to low--heat airflow
five seconds after the R to W2 circuit opens.
Cooling Mode
The thermostat calls for cooling.
1. Single--Speed Cooling
(See Fig. 19 for thermostat connections.)
The thermostat closes R--to--G--and--Y circuits. The R--to--Y
circuit starts the outdoor unit, and R--to--G--and--Y/Y2 cir-
cuits start the furnace blower motor BLWM on cooling air-
flow. Cooling airflow is based on the A/C selection shown
in Fig. 39.
The electronic air cleaner terminal EAC--1 is energized with
115--v when blower motor BLWM is operating.
When the thermostat is satisfied, the R--to--G--and--Y cir-
cuits are opened. The outdoor unit will stop, and furnace
blower motor BLWM will continue operating at cooling air-
flow for an additional 90 sec. Jumper Y/Y2 to DHUM to
reduce the cooling off--delay to 5 seconds. (See Fig. 33.)
2. Single--Stage Thermostat and Two--Speed Cooling (Ad-
aptive Mode)
(See Fig. 50 for thermostat connections.)
This furnace can operate a two--speed cooling unit with a
single--stage thermostat because the furnace control CPU in-
cludes a programmed adaptive sequence of controlled oper-
ation, which selects low--cooling or high--cooling operation.
This selection is based upon the stored history of the length
of previous cooling period of the single--stage thermostat.
NOTE: The air conditioning relay disable jumper ACRDJ must
be connected to enable the adaptive cooling mode in response to a
call for cooling. (See Fig. 33.) When in place the furnace control
CPU can turn on the air conditioning relay ACR to energize the
Y/Y2 terminal and switch the outdoor unit to high--cooling.
The furnace control CPU can start up the cooling unit in
either low-- or high--cooling. If starting up in low--cooling,
the furnace control CPU determines the low--cooling
on--time (from 0 to 20 minutes) which is permitted before
switching to high--cooling.
If the power is interrupted, the stored history is erased and
the furnace control CPU will select low--cooling for up to
20 minutes and then energize the air conditioning relay
ACR to energize the Y/Y2 terminal and switch the outdoor
unit to high--cooling, as long as the thermostat continues to
call for cooling. Subsequent selection is based on stored
history of the thermostat cycle times.
The wall thermostat “calls for cooling,” closing the R to
G--and--Y circuits. The R to Y1 circuit starts the outdoor
unit on low--cooling speed, and the R to G--and--Y1
circuits starts the furnace blower motor BLWM at
low--cooling airflow which is the true on--board CF
selectionasshowninFig.39.
If the furnace control CPU switches from low--cooling to
high--cooling, the furnace control CPU will energize the air
conditioning relay ACR. When the air conditioning relay
ACR is energized the R to Y1--and--Y2 circuits switch the
outdoor unit to high--cooling speed, and the R to
G--and--Y1--and--Y/Y2 circuits transition the furnace
blower motor BLWM to high cooling airflow.
355BAV

Other manuals for Bryant 355BAV

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bryant 355BAV and is the answer not in the manual?

Bryant 355BAV Specifications

General IconGeneral
BrandBryant
Model355BAV
CategoryFurnace
LanguageEnglish

Related product manuals