EasyManua.ls Logo

Bryant 376CAV - Page 10

Bryant 376CAV
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CAUTION: Connect the gas pipe to the furnace using a
backup wrench to avoid damaging gas controls.
WARNING: Never purge a line into a combustion
chamber. Never use matches, candles, flame, or other
sources of ignition for to check for gas leakage. Use a
soap-and-water solution to check for gas leaks. Failure to
follow this warning could result in fire, explosion, per-
sonal injury, or death.
Joint compounds (pipe dope) should be applied sparingly and only
to the male threads of the joints. This pipe dope must be resistant
to the action of propane gas.
An accessible manual shutoff valve MUST be installed upstream
of the furnace gas controls and within 72 in. of the furnace. A
1/8-in. NPT plugged tapping, accessible for test gage connection,
MUST be installed immediately upstream of the gas supply
connection to the furnace and downstream of the manual shutoff
valve. Place a ground joint union between the gas control manifold
and the manual shutoff.
Install a sediment trap in the riser leading to the furnace. The trap
can be installed by connecting a tee to the riser leading from the
furnace. Connect a capped nipple into the lower end of the tee. The
capped nipple should extend below the level of the gas controls.
(See Fig. 13.)
Piping should be pressure tested in accordance with local and
national plumbing and gas codes before the furnace has been
attached. If the pressure exceeds 0.5 psig (14-in. wc), the gas
supply pipe must be disconnected from the furnace and capped
Fig. 11Horizontal Filter Arrangement
A82173
;
;;;
;
;;
;;
;;;;;;
;;;;;
;;
;;;
;;;
FIELD-SUPPLIED
FILTER RETAINERS
AIRFLOW
D
12
4
TABLE 4FILTER INFORMATION (IN.)
FURNACE CASING
WIDTH
FILTER SIZE AND QUANTITY D
14-3/16 (2)16X20X1 153/8
17-1/2 (2)16X20X1 143/4
21 (2)16X20X1 133/4
24-1/2 (2)16X20X1 121/2
Fig. 12Downflow Filter Arrangement
A88486
RETURN-AIR
PLENUM
;;;;
;;;;
;;;;
;;;;
;;;;
;;;;
;;;;
;;;;
;;;;
AIRFLOW
ACCESS DOOR
INSTALLATION
POSITION
OF FILTERS
TABLE 5MAXIMUM CAPACITY OF PIPE*
NOMINAL IRON
PIPE SIZE
(IN.)
INTERNAL
DIAMETER
(IN.)
LENGTH OF PIPE (FT)
10 20 30 40 50
1/2 0.622 175 120 97 82 73
3/4 0.824 360 250 200 170 151
1 1.049 680 465 375 320 285
11/4 1.380 1400 950 770 660 580
11/2 1.610 2100 1460 1180 990 900
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a
pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table
10-2 NFPA 54/ANSI Z223.1-1996.
Fig. 13Typical Gas Pipe Arrangement
A89414
GAS
SUPPLY
MANUAL
SHUTOFF
VALVE
(REQUIRED)
SEDIMENT
TRAP
UNION
10

Other manuals for Bryant 376CAV

Related product manuals