GUIDE SPECIFICATIONS (CONT)
N. Low NOx:
Shall provide NOx reduction to values below 40 nanograms/
joule to meet California’s and other localities’ emission re-
quirements as shipped from factory.
O. Special Features Available:
1. Coil Options
Base unit with tin plated indoor coil hairpins available as a
factory installed option.
2. Compressor Start Kit (single phase units only):
Shall provide additional starting torque for single--phase
compressors.
3. Thermostat:
To provide for one--stage heating and cooling in addition
manual or automatic changeover and indoor fan control.
4. Crankcase Heater:
Shall provide anti--floodback protection for low--load cool-
ing applications.
5. Economizer:
a. Economizer controls capable of providing free cooling
using outside air.
b. Equipped with low leakage dampers not to exceed 3%
leakage, at 1.0 IN. W.C. pressure differential.
c. Spring return motor shuts off outdoor damper on power
failure.
6. Filter Rack Kit:
Shall provide filter mounting for downflow applications.
7. Flat Roof Curb:
Curbs shall have seal strip and a wood nailer for flashing
and shall be installed per manufacturer’s instructions.
8. Flue Discharge Deflector
Directs flue gas exhaust; 90 degrees upward from current
discharge.
9. Heat Exchanger
Stainless Steel Heat Exchanger available as a factory
installed option.
10. High Altitude Propane Conversion Kit:
Shall consist of all required hardware to convert to propane
gas heat operation at 2001 to 6000 ft (611 to 1829 m) above
sea level.
11. Low Ambient Package:
Shall consist of a solid--state control and condenser coil
temperature sensor for controlling condenser-- fan motor op-
eration, which shall allow unit to operate down to 0_F
(-- 18_C) outdoor ambient temperature when properly
installed.
12. Manual Outdoor Air Damper:
Package shall consist of damper, birdscreen, and rainhood
which can be preset to admit outdoor air for year--round
ventilation.
13. Natural--to --Propane Conversion Kit:
Shall be complete with all required hardware to convert to
propane gas operation at 10.0 IN. W.C. manifold pressure.
14. Propane--to-- Natural Conversion Kit
Shall be complete with all hardware to convert to natural
gas at standard altitude (0 to 2000 ft [0 to 610 m] above sea
level).
15. Square--To--Round Duct Transitions (24-- 48 models):
Shall have the ability to convert the supply and return open-
ings from rectangular to round.
16. Time Guard II
Automatically prevents the compressor from restarting for
at least 4 minutes and 45 seconds after shutdown of the
compressor. Not required when a corporate programmable
thermostat is applied.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
E2009 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 06/09
Replaces: PDS577C ---02
Catalog No. PDS577C---03
577C-- --A