40
Table 13 -- Dry Coil Air Delivery -- Horizontal and Downflow Discharge -- 208/230 VAC Single Phase Models (Cont)
Unit
Heating Rise
Range
Motor
Speed
Wire
Color
Allowable Functions
External Static Pressure (in. WC)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
42090
35 --- 65
o
F
Low Stage,
35 --- 65
o
F
High Stage
Low
3
Blue
Low Stage Gas Heating
Alternate Low Stage
Cooling
CFM 882 737 665 608 542 496 437 395 339 288
BHP 0.10 0.10 0.11 0.12 0.13 0.14 0.14 0.15 0.16 0.17
Low Stage
Heat Rise
o
F
(
o
C)
50
(28)
60
(33)
NA NA NA NA NA NA NA NA
High Stage
Heat Rise
o
F
(
o
C)
NA NA NA NA NA NA NA NA NA NA
Med---Low
1
Pink
Low Stage Cooling
Alternate Low Stage
Gas Heating
CFM 1076 1026 972 918 872 827 771 714 666 611
BHP 0.13 0.14 0.15 0.15 0.17 0.18 0.18 0.20 0.21 0.22
Low Stage
Heat Rise
o
F
(
o
C)
41
(23)
43
(24)
46
(25)
48
(27)
51
(28)
54
(30)
58
(32)
62
(35)
NA NA
High Stage
Heat Rise
o
F
(
o
C)
NA NA NA NA NA NA NA NA NA NA
Medium
4
Red
High Stage Gas Heating
Alternate High Stage
Cooling
Alternate Low Stage
Gas Heating
CFM 1359 1311 1267 1224 1187 1140 1095 1058 1019 973
BHP 0.25 0.26 0.27 0.28 0.29 0.31 0.31 0.33 0.34 0.35
Low Stage
Heat Rise
o
F
(
o
C)
NA NA
35
(19)
36
(20)
37
(21)
39
(22)
41
(23)
42
(23)
44
(24)
46
(25)
High Stage
Heat Rise
o
F
(
o
C)
50
(28)
52
(29)
54
(30)
55
(31)
57
(32)
60
(33)
62
(34)
64
(36)
NA NA
M e d --- H i g h
2
Orange
High Stage Cooling
Alternate High Stage
Gas Heating
CFM 1451 1415 1372 1327 1287 1249 1212 1168 1130 1094
BHP 0.29 0.30 0.31 0.32
248.
59
0.35 0.36 0.37 0.38 0.39
Low Stage
Heat Rise
o
F
(
o
C)
NA NA NA NA NA NA NA NA NA NA
High Stage
Heat Rise
o
F
(
o
C)
46
(26)
47
(26)
49
(27)
51
(28)
52
(29)
54
(30)
55
(31)
57
(32)
59
(33)
61
(34)
High Black
High Static, High Stage
Cooling Only
CFM 1633 1590 1552 1518 1483 1444 1406 1372 1340 1303
BHP 0.41 0.43 0.44 0.45 0.47 0.48 0.49 0.50 0.51 0.53
Notes:
*Air delivery values are without air filter and are for dry coil (See Wet Coil Pressure Drop Table)
“High Static, High Stage Cooling” --- Only to be used for high stage cooling function (Not allowed for any gas heating function)
1
F actory-shipped low stage cooling speed
2
Factory-shipped high stage cooling speed
3
Factory-shipped low stage gas heating speed
4
Factory-shipped high stage gas heating speed
Shaded areas indicate speed/static combinations that are not permitted for dehumidification speed.
”NA” = Not allowed for particular gas heating speed
577E