41
Table 13 -- Dry Coil Air Delivery -- Horizontal and Downflow Discharge -- 208/230 VAC Single Phase Models (Cont)
Unit
Heating Rise
Range
Motor
Speed
Wire
Color
Allowable Functions
External Static Pressure (in. WC)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
48090
35 --- 65
o
F
Low Stage,
35 --- 65
o
F
High Stage
Low
3
Blue Low Stage Gas Heating
CFM 903 820 749 702 645 581 534 468 432 382
BHP 0.11 0.12 0.12 0.13 0.14 0.14 0.16 0.16 0.17 0.18
Low Stage
Heat Rise
o
F
(
o
C)
49
(27)
54
(30)
59
(33)
63
(35)
NA NA NA NA NA NA
High Stage
Heat Rise
o
F
(
o
C)
NA NA NA NA NA NA NA NA NA NA
Med---Low
1
Pink
Low Stage Cooling
Alternate Low Stage
Gas Heating
Alternate High Stage
Gas Heating
CFM 1271 1229 1177 1121 1066 1027 974 942 887 839
BHP 0.19 0.20 0.21 0.23 0.24 0.25 0.26 0.27 0.28 0.29
Low Stage
Heat Rise
o
F
(
o
C)
35
(19)
36
(20)
38
(21)
40
(22)
42
(23)
43
(24)
46
(25)
47
(26)
50
(28)
53
(29)
High Stage
Heat Rise
o
F
(
o
C)
53
(30)
55
(31)
58
(32)
61
(34)
63
(35)
64
(35)
NA NA NA NA
Medium
4
Red
High Stage Gas Heating
Alternate High Stage
Cooling
Alternate Low Stage
Gas Heating
CFM 1386 1336 1304 1259 1230 1186 1147 1102 1052 1022
BHP 0.32 0.33 0.34 0.35 0.36 0.37 0.39 0.39 0.40 0.42
Low Stage
Heat Rise
o
F
(
o
C)
NA NA NA
35
(20)
36
(20)
37
(21)
39
(21)
40
(22)
42
(23)
43
(24)
High Stage
Heat Rise
o
F
(
o
C)
49
(27)
51
(28)
52
(29)
54
(30)
55
(31)
57
(32)
59
(33)
62
(34)
64
(36)
NA
M e d --- H i g h
2
Orange
High Stage Cooling
Alternate High Stage
Gas Heating
CFM 1686 1650 1617 1576 1544 1503 1468 1433 1393 1356
BHP 0.42 0.44 0.45 0.46 0.48 0.49 0.51 0.52 0.53 0.55
Low Stage
Heat Rise
o
F
(
o
C)
NA NA NA NA NA NA NA NA NA NA
High Stage
Heat Rise
o
F
(
o
C)
40
(22)
41
(23)
42
(23)
43
(24)
44
(24)
45
(25)
46
(26)
47
(26)
49
(27)
50
(28)
High Black
High Static, High Stage
Cooling Only
CFM 1854 1837 1781 1784 1720 1698 1655 1625 1578 1532
BHP 0.56 0.57 0.60 0.59 0.62 0.63 0.64 0.66 0.67 0.67
Notes:
*Air delivery values are without air filter and are for dry coil (See Wet Coil Pressure Drop Table)
“High Static, High Stage Cooling” --- Only to be used for high stage cooling function (Not allowed for any gas heating function)
1
F actory-shipped low stage cooling speed
2
Factory-shipped high stage cooling speed
3
Factory-shipped low stage gas heating speed
4
Factory-shipped high stage gas heating speed
Shaded areas indicate speed/static combinations that are not permitted for dehumidification speed.
”NA” = Not allowed for particular gas heating speed
577E