EasyManuals Logo

Bryant 579D Installation Instructions

Bryant 579D
8 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
III. ENTHALPY CONTROL CHECKOUT PROCEDURES
A. Solid-State Enthalpy Control
Use this procedure for the solid-state enthalpy control that
comes standard with the economizer. (See table below.)
Solid-State Enthalpy Control Contents
PART NO.
HF25CA003
Economizer Motor
Economizer Logic Module
HH57AC078 Solid-Stage Enthalpy Sensor
HH79AZ001 Mixed-Air Sensor
1. Disconnect power at terminals TR and TR1. Dis-
connect jumper across terminals P and P1.
2. Jumper terminals TR and 1.
3. Connect enthalpy sensor to terminals SO and +. The
factory-installed 620-ohm resistor should be in place
on terminals SR and +.
4. Turn enthalpy set point to ‘‘A.’’
5. Jumper terminal T to terminal T1.
6. Spray a small amount of refrigerant in the upper left
vent of the enthalpy sensor to simulate low enthalpy
conditions. (See Fig. 15.)
7. Connect 24-v power at terminals TR and TR1. The LED
(light-emitting diode) will turn on and the economizer
motor will drive the damper full open.
8. Disconnect the jumper at terminals T and T1. The econo-
mizer motor will drive the damper full closed.
9. Connect a jumper across terminals P and P1.
10. Turn minimum position potentiometer adjustment coun-
terclockwise and the economizer motor drives the damper
closed.
11. Turn minimum position potentiometer adjustment clock-
wise and the economizer motor drives the damper open.
12. Disconnect the power at terminals TR and TR1. The
economizer motor spring-returns the damper to closed
position.
B. Differential Enthalpy Control
Use this checkout procedure for the accessory differential
enthalpy control. The differential enthalpy control kit con-
tains one solid-state enthalpy sensor (part no. HH57AC078)
to be installed in addition to the solid-state enthalpy control
which comes standard with the economizer. See table on
this page for standard solid-state enthalpy control package
contents.
1. Disconnect the power at terminals TR and TR1. See
Fig. 12.
2. Disconnect the jumper across terminals P and P1.
3. Disconnect the factory-installed 620-ohm resistor.
4. Connect one enthalpy sensor to terminals SO and +.
5. Connect the other enthalpy sensor to terminals SR
and +.
6. Turn the enthalpy set point past the ‘‘D’ setting (fully
clockwise).
7. Connect a jumper across terminals T and T1.
8. Spray a small amount of refrigerant in upper left vent
of enthalpy sensor connected to SO and + to simulate
low outdoor-air enthalpy. (See Fig. 15.)
9. Reconnect power at terminals TR and TR1. The LED
(Light-emitting diode) turns on, and the economizer
motor drives the damper open.
10. Spray a small amount of refrigerant in upper left vent
of enthalpy sensor connected to SR and + to simulate
low return-air enthalpy. (See Fig. 15.) The LED turns
off, and the economizer motor drives the damper closed.
Fig. 15 Use of Refrigerant Spray on Sensor to
Simulate Low Enthalpy
—7—

Other manuals for Bryant 579D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bryant 579D and is the answer not in the manual?

Bryant 579D Specifications

General IconGeneral
BrandBryant
Model579D
CategoryAir Conditioner
LanguageEnglish

Related product manuals