EasyManua.ls Logo

Bryant DURAPAC 579F - Step 13 - Adjust Factory-Installed Options

Bryant DURAPAC 579F
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
—14—
Install Motormaster V Controls
The Motormaster V control is a motor speed control device
which adjusts condenser fan motor speed in response to
declining liquid refrigerant pressure. A properly applied
Motormaster V control extends the operating range of air-
conditioning systems and permits operation at lower outdoor
ambient temperatures.
The minimum ambient temperatures at which the unit will
operate are:
To operate down to the ambient temperatures listed,
Motormaster V controls (Fig. 23) must be added. Field-
fabricated and installed wind baffles are also required for all
units (see Fig. 21). The Motormaster V control permits opera-
tion of the unit to an ambient temperature of –20 F. The control
regulates the speed of 3-phase fan motors that are compatible
with the control. These motors are factory installed.
See Table 6 for the Motormaster V control accessory package
usage. Table 7 shows applicable voltages and motors.
Replacement of a motor IS NOT REQUIRED ON CUR-
RENT PRODUCTION UNITS since the control is compati-
ble with the factory-installed fan motors. Only field wiring
control is required.
Install the Motormaster V control per instructions supplied
with accessory.
Table 6 — Motormaster V Control Package Usage
Table 7 — Applicable Voltages and Motors
XIII. STEP 13 — ADJUST FACTORY-INSTALLED OPTIONS
A. Optional EconoMi$erIV
See Fig. 24 and 25 for EconoMi$erIV component locations.
NOTE: These instructions are for installing the optional
EconoMi$erIV only. Refer to the accessory EconoMi$erIV
installation instructions when field installing an EconoMi$erIV
accessory.
To complete installation of the optional EconoMi$erIV, per-
form the following procedure.
1. Remove the EconoMi$erIV hood. Refer to Step 11 —
Install Outdoor-Air Hood on page 11 for information
on removing and installing the outdoor-air hood.
2. Relocate outdoor air temperature sensor from ship-
ping position to operation position on EconoMi$erIV.
See Fig. 24.
IMPORTANT: Failure to relocate the sensor will result in the
EconoMi$erIV not operating properly.
3. Re-install economizer hood.
4. Install all EconoMi$erIV accessories. EconoMi$erIV
wiring is shown in Fig. 26.
Outdoor air leakage is shown in Table 8. Return air pressure
drop is shown in Table 9.
TEMPERATURE OPERATING LIMITS — F°
Standard Unit Unit with Low Ambient Kit Unit with MMV Control
40 25 –20
UNIT VOLTAGE ITEM DESCRIPTION
579F180-300
208/230 CRLOWAMB015A00
460 CRLOWAMB016A00
VOLTAGE COMPATIBLE MOTOR
208/230-3-60 HD52AK654
460-3-60 HD52AK654
SENSOR
LOCATION
HAIRPIN END
SENSOR
LOCATION
HAIRPIN END
NOTE: Dimensions in ( ) are in mm.
Fig. 21 — Wind Baffle Details
579F180 579F216
NOTE: All sensors are located on the eighth hairpin up from the
bottom.
Fig. 22 — Motormaster® I Sensor Locations