11
Table 6 Temperature / Ohm Relationship
Tem p . (°F/°C) Resistance (Ohms)
--- 9 / --- 2 3 78330
--- 8 / --- 2 2 74610
--- 6 / --- 2 1 71100
--- 4 / --- 2 0 67770
--- 2 / --- 1 9 64570
--- . 4 / --- 1 8 61540
1 / --- 1 7 58680
3 / --- 1 6 55970
5 / --- 1 5 53410
7 / --- 1 4 50980
9 / --- 1 3 48680
10 / ---12 46500
12 / ---11 44430
14 / ---10 42470
1 6 / --- 9 40570
1 8 / --- 8 38770
1 9 / --- 7 37060
2 1 / --- 6 35440
2 3 / --- 5 33900
2 5 / --- 4 32440
2 7 / --- 3 31050
2 8 / --- 2 29730
3 0 / --- 1 28480
32 / 0 27280
34 / 1 26130
36 / 2 25030
37 / 3 23990
39 / 4 23000
41 / 5 22050
43 / 6 21150
45 / 7 20300
46 / 8 19480
48 / 9 18700
50 / 10 17960
52 / 11 17240
54 / 12 16560
55 / 13 15900
57 / 14 15280
59 / 15 14690
61 / 16 14120
63 / 17 13580
64 / 18 13060
66 / 19 12560
68 / 20 12090
70 / 21 11630
72 / 22 11200
73 / 23 10780
75 / 24 10380
77 / 25 10000
79 / 26 9632
81 / 27 9281
82 / 28 8944
84 / 29 8622
86 / 30 8313
88 / 31 8014
90 / 32 7728
91 / 33 7454
93 / 34 7192
95 / 35 6940
97 / 36 6699
99 / 37 6467
100 / 38 6245
Table 7 Defrost Cycle
HRV DEFROST CYCLES
Outside Temp
°F/°C
Defrosting
(minutes)
Operation time (min.)
between each
defrost cycle
23 to ---17°F
--- 5 t o --- 2 7 °C
7 25
--- 1 7 °Fandless
--- 2 7 °Candless
10 22
ERV DEFROST CYCLES
Outside Temp
°F/°C
Defrosting
(minutes)
Operation time (min.)
between each
defrost cycle
23 to ---17°F
--- 5 t o --- 2 7 °C
9 23
--- 1 7 °Fandless
--- 2 7 °Candless
10 22
ERV / HRV