EasyManua.ls Logo

Bunn ULTRA-2A - Compressor (Embraco) Testing; Windings and Component Testing

Bunn ULTRA-2A
73 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36
SERVICE (cont.)
COMPRESSOR (EMBRACO) (ULTRA-2)
Compressor Windings & Related Component Testing:
Note: Measure the resistance (ohms) between termi-
nal pins C&S and C&R around ambient temperature
of 77° F. Add the resistance between C & S and C & R.
The sum should equal the resistance found between S
& R. A 10% deviation is acceptable.
Continuity must be present between C & S and C & R.
If there is no continuity on start or run winding, there
is an interruption within that winding.
Check the C (common) compressor winding to com-
pressor ground terminal/housing. If continuity is
present, one of the compressor windings is shorted
to ground.
Check Compressor Windings for Ground Fault:
Upon removal of the protective terminal cover, if evi-
dence is shown by any lead or terminal being over-
heated, it is a good indication that a compressor wind-
ing problem may exist. Follow the recommended step
below to check the compressor winding insulation. If
a ground fault is detected with the compressor, keep
the power off, thermal protector and potential relay
disconnected. A licensed certified refrigerant techni-
cian will need to replace a defective compressor.
Testing Compressor Windings/Insulation with a Meg-
ger
A megger is a preferred test over using a typical ohm
meter for testing the compressor windings. The meg-
ger checks the insulation factor of a winding making
sure it is actually insulated and not leaking current
(Ground Fault). An ohm meter usually produce a low
voltage for reading resistance verses a megger uses
higher direct voltage source to measure insulation re-
sistance to detect a breakdown in the motor winding
insulation.
Step 1: Disconnect all electrical power to the BUNN
ULTRA-2 HP.
Step 2: Access compressor terminal pins and discon-
nect the wire leads going to the compressor pins.
Step 3: Set the megger to the compressor applicable
voltage rating. If the megger you are using only has
a few specific voltage ranges, select the next highest
voltage above your compressor volt range.
Step 4: Connect one lead of the megger to the copper
suction line or housing. Connect the other lead to one
of the compressor terminal pins (winding).
Step 5: Repeat the procedure for the two remaining
terminal pins. If the instrument indicates any resis-
tance less than 2 megohms between any pin and the
housing (copper suction line), a ground fault exists.
Replace compressor.

Related product manuals