- 12 -
C-LOGIC 400-TC EN
Period Symbol Default period time
Defaul period
temperature
Weekend
1
08:00 22ºC
2
23:00 15ºC
Note: If setting temperature is “00”, this time interval is shutdown.
Advanced setting (Suggestion: operated by technician)
Under power off state, press and hold “ ” Under power off state, press and
hold “ ” in order to enter in the advanced setting menu. Each parameter can
be changed by pressing “
” and ” ” keys and conrmed by pressing “SET”
key, progressing to the next parameter. The advanced settings in this menu are
indicated below:
No Symbol Description Parameter range
Factory
default
1 dIF
Temperature
hysteresis
0.5ºC – 4.5ºC 1.0ºC
2 SUH
Set upper
temperature
value
5ºC – 99ºC 1. 35ºC
3 SUL
Set lower
temperature
value
5ºC – 99ºC 2. 5ºC
4 AdJ
Room
temperature
adjust
(Calibration)
-5ºc – 5ºC 3. 0.0ºC
5 FrE
Anti-freezing
function
00: Anti-freezing function
shutdown
01: Anti-freezing function
enabled
00
6 LOC
Lock function
00: Lock disabled
01: Half lock
02: Full lock
00
7 FAC
Factory
default
08: Maintaining current
settings
00: Restore Factory default
08