ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 38 of 48
CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
MONITOR A POINT
This function allows you to view the current analogue status of any point (any addressable device on
the system).
Enter AL3 (4444) > Engineer Functions > Monitor a Point.
When selected, choose the loop number (1 or 2), press the Accept4 button to continue then press the
5,6 and Accept4 buttons to select the device’s address.
The panel will temporarily disable the point in question and return back its analogue values, for
example:
Note 1: The analogue values returned will differ dependent on whether the device is a detector,
manual call point, I/O unit or sounder.
Note 2: The information displayed will assist C-TEC Technical Support to identify the cause of any
problems.
L : 1 D:7 AV:63 21:Cal:150
F: 0 TC: 0x03
The loop being
monitored
The device's
address
The device's
current analogue value
(nominally ‘0’)
The device's gain
value
The fault code for any fault
condition that device may be in
The devices's type code
Loop:1 Device : 7
Loop : 1