S320 OCS Repair and Diagnostics Field Guide
Doc. Part No. 460163-00
May 5, 2015
Rev. B1
Page 21 of 22
Symptom
Severity
Corrective Action
Connection output power not
maintainable
CR
Check input power for bad transceivers;
contact CALIENT Support, if needed
Light loss through the matrix is
below the critical threshold
MJ
Contact CALIENT Support
Light loss through the matrix is
below the degraded threshold
MJ
Contact CALIENT Support
Optical Monitoring Module
(OMM) is not detecting
appropriate levels of light,
resulting in critical transit
connection receive signal.
Transit connection transmit
signal is critical. The value of
a degraded receive signal is
-18 dBm at shipment; this value
can be adjusted by the user at
Home > All Ports > Port Detail.
MJ
Check input port power, fiber and
connector
Transit connection receive
signal is degraded. The value
of a degraded receive signal is
-15 dBm at shipment; this value
can be adjusted by the user at
Home > All Ports > Port Detail.
MJ
Check input port power, fiber and
connector
Transit connection transmit
signal is critical. The value of
a degraded receive signal is
-18 dBm at shipment; this value
can be adjusted by the user at
Home > All Ports > Port Detail.
MJ
Check input and output port power;
recreate connection, if needed
Transit connection receive
signal is degraded. The value
of a degraded receive signal is
-15 dBm at shipment; this value
can be adjusted by the user at
Home > All Ports > Port Detail.
MN
Check input and output port power;
recreate connection, if needed
Transit connection receive
signal is too high
MJ
Check input power