S-Series Technical Manual 35 Cambridge Engineering, Inc.
OPERATING INSTRUCTIONS
TSS CONTROLLER
The Cambridge Engineering TSS Controller provides several features to tailor the operation of the Cambridge
heating system to particular applications.
• Seven day programmable clock.
• Separate temperature settings for Heating and Setback operation.
• Separate schedules for Summer Ventilation and Heating modes.
• Setback Override for temporary heating operation.
• Real-Time Clock with automatic adjustment for Daylight Saving Time.
• Nine Holiday Setback Periods for temporary setback operation.
• Temperature Calibration for accurate temperature control.
• Capacitor backup maintains current time and day of week for power loss of up to 96 hours.
• EEPROM storage maintains schedules and temperature settings indefinitely.
The thermistor enclosure (SH-1) is packed inside the Remote Control Station for shipment. It can be mounted
on the exterior sides or bottom of the Remote Control Station or a remote location within 500 feet of the Remote
Control Station using 18 gauge stranded, twisted-pair, shielded cable. The thermistor is hard wired to the tempera-
ture sensor terminal block.