S-Series Technical Manual 43 Cambridge Engineering, Inc.
TEMPERATURE CALIBRATION
To compensate for lead wire resistance, it may be neces-
sary to make an adjustment to the displayed temperature
to correct it to the temperature measured at the thermis-
tor sensor. The calibration feature allows the displayed
temperature to be offset either above or below the actual
sensed temperature. Be sure to use an accurate tempera-
ture meter for making this correction.
1. Press and hold the
HEAT ON and HEAT OFF buttons
while pressing the UP or the DOWN button until the
correct temperature is displayed. (A period [.] after the
F will indicate the Calibration Mode).
2. Pressing the UP or the DOWN button will display the
current calibration difference above or below (-) the
measured temperature.