3.  On the Datalogger tab, change the data logger PakBus Address and PakBus/TCP Password 
to match the values entered in the Konect PakBus Router setup. The PakBus/TCP Password 
will make the data logger authenticate any incoming or outgoing PakBus/TCP connection.
4.  On the Network Services tab in the PakBus/TCP Client field, enter the DNS address and 
Port number noted during the Konect PakBus Router setup.
5.  On the PPP tab, set Config/Port Used to CS I/O SDC8 or RS-232, depending on how you 
are connected to the data logger.
6.  (Optional) On the PPP tab, set User Name and Password if required by your cellular carrier 
(usually outside of the United Sates). 
7.  (Optional) If your cellular carrier requires user name and password authentication, on the 
Settings Editor > Cellular tab, set PDP Authentication Type, PPP Authentication Username 
and PPP Authentication Password.
8.  Verify the Modem Dial String setting is blank.
9.  If connecting through RS-232, on the Comport Settings tab, set RS232 BaudRate to 
115200Fixed.
10.  Click Apply. 
11.  Shut down Device Configuration Utility and start it again. This will activate the Cellular tab 
needed for the next step. 
12.  On the Cellular tab, enter the APN provided by your cellular provider. For standard Telstra 
SIMs, this will be telstra.internet.
3. Cellular communications option9