The following steps are performed at the factory and verifying on site will
be sufficient:
6) Select Pump Configuration
7) Press [Advanced Options >>]
8) Press the to arrive at Central Heat Pump or DHW Pump
9) On Options: Local burner demand
10) On Options: Local Lead Lag Service Active
11) Force On: Outlet high limit
Master Boiler, System Sensor
Master boiler system sensor
configuration
1) Press
and
2) Press [Sensor Configuration]
3) Select S5 (J8-11) Sensor
4) Connector Type: 10K NTC Single Non-Safety
5) The control will proceed into a Lockout 2 condition
6) Press [Verify] > [Begin] > [Yes]
7) Press the reset button on the ignition control within the alotted time