CY-12TAOUT CY-18FAOUT
CY-2T14AOUT
Model CY-09TAOUT CY-09FAOUT CY-18TAOUT
CY-2T18AOUT
CY-12FAOUT CY-24TAOUT CY-2M14AOUT
CY-2M18AOUT
Connecting wiring 4G1.0mm² 4G1.0mm² 4G1.0mm²
P
ow
er cable 3G1.0mm² 3G1.5mm² 3G2.5mm²
FOR
CY-09TAOUT CY-24TAOUT
FOR
CY-18FAOUT
CY-12TAOUT CY-09FAOUT
CY-18TAOUT CY-12FAOUT
Outdoor unit
Outdoor unit
POWER
To Indoor unit
To Indoor unit
POWER
item Circuit breaker Earth leakage breaker
Phase
Overcurrent protector
rated capacity (A)
Model
Switch breaker(A) Switch breaker(A) Leak current(mA)
CY-09TAOUT CY-09FAOUT
CY-12TAOUT CY-12FAOUT
1 20 15 20 30
CY-18FAOUT
CY-18TAOUT CY-24TAOUT
CY-2T14AOUT CY-2T18AOUT
CY-2M14AOUT CY-2M18AOUT
1 25 20 25 30
ceramic type of T 25A/250V.
.
The explosion-proof breaker of the air conditioner should be all-pole switch. The distance between its two contacts should not be no
A explosion-proof breaker must be installed.
FOR
CY-2T14AOUT
CY-2T18AOUT
CY-2M14AOUT
CY-2M18AOUT
Power supplyRoom A
Room B
TO Indoor unit A
TO Indoor unit B Power
1(N)
2(L)