3. Serial network con guration
Hecu CO2 is fi tted with a built-in RS485 Fieldbus serial port and optional
RS485 BMS serial port. The RS485 Fieldbus serial line can be connected
to 2 Power+ inverters and up to 5 MPXPRO/UltraCella controllers. The
addresses are defi ned as shown in the following table. To simplify
commissioning with the default settings, it is recommended to set the
MPXPRO/UltraCella controllers with consecutive addresses, starting
from address 11. The following table shows the default values of serial
addresses for the connected MPXPRO/UltraCella controllers.
Device Address Device Address
Power+ 1 MPXPRO/UltraCella 3 13
Power+ 3 MPXPRO/UltraCella 4 14
MPXPRO/UltraCella 1 11 MPXPRO/UltraCella 5 15
MPXPRO/UltraCella 2 12
Serial address 3 is used for the parallel compressor inverter when this is
featured in the LT application.
Note: For LT units, the two inverter addresses must be 1 and 3. To
set these addresses (1 and 3), the corresponding dipswitches are set to 0
and 2, which when added to the basic address (1) will give the fi nal
addresses 1 and 3 (see the paragraph "Network address" on page 13).
C1
C2
L1/L L2/N L3 U V W
12 345 678910
F
PE
C1
C2
AUX
master
MPXPRO
High
voltage
AUX
master
master
EVDEVO EVDEVOmaster
MPXPRO
High
voltage
Fieldbus - Modbus® RS485
max 5 units
Supervisory
system
1
C1
C2
L1/L L2/N L3 U V W
12 345 678910
F
PE
C1
C2
3
11
12
13
14
RPRV valve
J1
J9
J11
J12
J14
J16
J17
J18
J19
J20
J21
J22
J23
J24
J10
J13
J2
J3
J4
J5
J6
J8
J7
ON
1
2
OFF
RX-/TX-
RX+/TX+
GND
Vout
RX-/TX-
RX+/TX+
GND
Fig. 2.n
Note: system communication is only compatible with MPXpro SW.
Important:
A possible short circuit on the Fieldbus serial line will compromise
operation of the system compressor.
As there is no software control on the connected device (MPXpro,
Ultracella), make sure during confi guration to set these correctly,
based on the physical address selected on the evaporator controller.
To set the power+, MPXpro and UltraCella addresses, see the
corresponding manuals.
Important: The system is only compatible with MPXpro SW revision
≥ 4.0 and UltraCella SW revision ≥ 2.0