43
ENG
Hecu CO
2
+0300085EN rel. 2.2 - 07.05.2019
The parameters involved are shown below.
Par. Description Def Min Max UOM
tLi Light on with door open 120 0 240 min
A4 Light management
0 Door switch + light button
1 Light button
001-
Note: if the controller is OFF, the light output is controlled only by
the light button. If the controller is ON, the light is controlled by
door switch + light button or light button only, according to the setting
of parameter A4.
Door switch + light button
If A4 = 1, the light is switched on/off only by the light button. The door
status, open or closed, is ignored. If A4 = 0, when the cold room door
is open, the light is always on. When the door is closed, the light can
be switched on or off using the light button. Once on, the light will
automatically switch off after the time set for Li.
LIGHT MANAGEMENT BY DOOR SWITCH AND LIGHT BUTTON
Light_K
Door_sw
Li
t
A4=0
tLi tLi
OFF
ON
OFF
ON
CL
OP
Fig. 7.m
Key
Light_k Light button
Li Light
Door_sw Door switch
tLi Light off delay
t time
7.3 Ultra EVD EVO module commissioning
EVD EVO driver con guration from UltraCella
Connect UltraCella to the EVD module via serial, as shown in the wiring
diagram in Figure 7.c, and refer to the following parameter table for
confi guration of the EVD EVO driver. The module will become active
when enabled by UltraCella, setting P1 = 1.
If connected via serial, the driver parameters can be displayed only (not
modifi ed) by the local EVD EVO display. Once the driver has been enabled
(parameter P1=1), its parameter settings will be sent by UltraCella, in
accordance with the parameter table below (only modifi able from
UltraCella); any parameters previously confi gured on the EVD EVO display
will be overwritten.
Par. Description Def Min Max UOM
P1
Enable communication with EVD EVO
module
1 = EVD module enabled
101-
EVD EVO parameter table
The following parameters relating to the EVD EVO driver can be
confi gured from UltraCella
Category: EVO
Par. Description Def Min Max UOM
P1 Enable communication with EVD EVO mod-
ule 0/1=disabled/enabled
001 -
P1t Type of probe S1
0 0-5 V rat. 2 4-20 mA remote
1 4-20 mA 3 4-20 mA external
003 -
P1M Maximum value of probe S1 12.8 -20 200 bar/psi
P1n Minimum value of probe S1 -1 -20 200 bar/psi
PVt Typeof valve
1 Carel exv
1 1 22 -
PH Type of refrigerant
1 R744
3 1 40 -
PrE Type of main control
1 cabinet/cold room with remote rack
2 cabinet/cold room with on-board
comp.
3 perturbed cabinet/cold room
4 subcritical CO
2
cabinet/cold room
214 -
P0 EVD Modbus address 198 1 247 -
P3 Superheat set point 10 -72 324 K
P4 Proportional gain 15 0 800 -
P5 Integral time 150 0 999 sec
P6 Derivative time 2 0 800 sec
P7 LowSH: low superheat threshold 3 -72 324 K
P8 LowSH: integral time 600 0 800 sec
P9 LowSH: low superheat alarm delay 600 0 999 sec
PL1 LOP: low evap. temperature threshold -50 -60 200 °C/°F
PL2 LOP: integral time 600 0 800 sec
PL3 LOP: low evaporation temperature alarm
delay
600 0 999 sec
PM1 MOP: max evap. pressure threshold 50 -60 200 °C/°F
PM2 MOP: integral time 600 0 800 sec
PM3 MOP: max evap. pressure alarm delay 10 0 999 sec
cP1 Initial valve position when control starts
(percentage)
50 0 100 %
Pdd Post defrost delay (single driver only) 10 0 60 min
PSb Valve position in standby 0 0 100 steps
PMP Enable manual positioning 0 0 1 -
PMu Manual valve position 0 0 999 steps
Pnr Reset EVD setting 0 -> 1 Reset all EVD EVO
parameters
001 -
PLt Stop smooth lines off set 2.0 0.0 10.0 °C/°F
PHS Maximum smooth lines off set 15.0 0.0 50.0 °C/°F
PSP Smooth lines proportional coeffi cient 5.0 0.0 100.0 °C/°F
PSI Smooth lines integral time 120 0 1200 s
PSd Smooth lines derivative time 0 0 100 s
PSM Enable smooth lines (0=NO - 1=YES) 0 0 1 /
Note: set parameters P1=1, P1M and P1n with the values of the
connected probe, PrE=1, PH=11 (R744)