¦To Be Inserted: ¦ heaters or no heaters.
¦ 0 ¦
+--------------------+
RAMPAFRE (MANUFACTURER BRANCH)
+--------------------+ Activation of the cooling valve.
¦-Modulable Valves AL¦
¦ ¦
¦Cooling Valve ¦
¦Enabled? No¦
+--------------------+
RAMPAFES (MANUFACTURER BRANCH)
+--------------------+ This mask is selected if the cooling valve in the
¦-- Cooling Valve AL¦ preceding mask has been activated.
¦Energy-Saving | It allows activation of the valve in case the
¦Enabled: ¦ Energy Saving option has been adopted.
¦(Yes/No)? No|
+--------------------+
COM_ES (MANUFACTURER BRANCH)
+--------------------+ This mask too is selected if the cooling valve in
¦-Modulable Valves AL¦ the RAMPAFRE mask has been activated.
¦Are Compressors ¦ It allows activation of the compressors even
¦Enabled also with ¦ together with the cooling valve.
¦Valve on ES ? No¦
+--------------------+
RAMPACAL (MANUFACTURER BRANCH)
+--------------------+ Activation of the heating valve.
¦-Modulable Valves AL¦
¦ ¦
¦Heating Valve ¦
¦Enabled? No¦
+--------------------+
GESTCOMP (MANUFACTURER BRANCH)
+--------------------+ This mask informs that the following masks are used
¦ AL¦ to activate compressors and their main functions.
¦ Compressors ¦
¦ Management ¦
¦ ¦
+--------------------+
NUMCOMPR (MANUFACTURER BRANCH)
+--------------------+ In this mask you can select the number of
¦-- Compressors -AL¦ compressors to be inserted.
¦Compressors Number ¦
¦to be Inserted:(0-2)¦
¦ 0 ¦
+--------------------+
PARZCOMP (MANUFACTURER BRANCH)
+--------------------+ This mask is always activated except when no
¦-- Compressors AL¦ compressors have been activated.
¦ ¦ It is used to activate partialisations.
¦Compressors Are ¦
¦Partialised? No¦
+--------------------+
RAMPAFIN (MANUFACTURER BRANCH)
+--------------------+ This mask is selected only if no compressors have
¦- 3-Point Valves AL¦ been activated.
¦Cooling 3-P Valve ¦ It is used to activate or not the cooling 3-point
¦Enabled? ¦ valve.
¦ No ¦
+--------------------+
RAMPACIN (MANUFACTURER BRANCH)
+--------------------+ This mask is selected only if no heaters have been
¦- 3-Point Valves AL¦ activated.
¦Heating 3-P Valve ¦ It is used to activate or not the heating 3-point
¦Enabled? ¦ valve.
¦ No ¦
+--------------------+
PROSPE (MANUFACTURER BRANCH)
+--------------------+ This mask informs you that the following masks are
¦ AL¦ used for Back-up memory clearing, default values
¦ Special ¦ setting, run-time values etc. ...
¦ Procedures ¦