Devices that can be connected to the pCOXS 512KB (tLAN and Belimo versions)
Device
connector J6
connector J5
PCO1004850
PCOS004850
PCO100MDM0
PCO10000F0
PCO10000R0
PCO100CLP0
PCO1000WB0
PCO1000BA0
PCOS00HBB0
connector J7
connett. J8 (pCOXS tLAN)
connett. J8 (pCOXS Belimo)
Protocol active on the pCO Notes
PST terminal X PST terminal Incompatible with CAREL Master 5 exp.
PLD terminal X
pCOT - pCOI terminal X Local terminal or pLAN
pGD0 - pGD1 terminal X Local terminal or pLAN With Local terminal the pGD* works in pCOT emulation mode
pGD2 - pGD3 terminal X Local terminal or pLAN
Aria terminal X
pCO in pLAN X pLAN
FCM series controllers X
EVD200 X
EVD400 X X
pLAN or CAREL Master or
CAREL Master 5 exp.
Can only be activated on one serial port. CAREL Master 5 exp.: incompatible with
PST terminal
CAREL Slave devices (tLAN) X
CAREL Master or CAREL
Master 5 exp.
Can only be activated on one serial port. CAREL Master 5 exp.: incompatible with
PST terminal
CAREL Slave devices (485) X X X
CAREL Master or
CAREL Master: can only be activated on one port, BMS serial or FieldBus serial or
pLAN.
pCOexp 485 X X X
CAREL Master 5 exp.
CAREL Master 5 exp.: can only be activated on one port, pLAN serial or FieldBus
serial
pCOexp tLAN X CAREL Master 5 exp.
Can only be activated on one serial port; incompatible with PST terminal
μChiller2 expansion X
Hydronic fan coil and CANbus X CAREL Master
Can only be activated on one serial port
PlantVisor local X X X
PlantWatch X X X Can only be activated
PCGate X X X on one serial port;
WebGate X X X at the same time, BMS or FieldBus
GATEWAY**0 X X X
LON - Echelon RS485 X If active on pLAN serial, these protocols cannot be used
LON - Echelon FTT10 X CAREL Slave PSTN
TREND X GSM
HTTP client X Modbus Slave
BACnet/Ethernet X on BMS serial
BACnet/IP X
BACnet/MSTP (RS485) X
SNMP v1, SNMP v2C X
SNMP v3 X For SNMP v3 special pCOWEB software is used
Modbus supervisor (RTU) X X X Modbus Slave
Modbus Slave devices X X X Modbus Master Can only be activated on one serial port
pCOexp Modbus X X X
BenShaw devices X X Modbus Master - Benshaw Maximum of two Benshaw devices
WinLoad local XXXX WinLoad Can only be activated on one serial port
WinLoad remote, analogue modem X PSTN
Can only be activated on one serial port
PlantVisor remote, analogue modem X
Incompatible with the GSM protocol; if activated on BMS serial is incompatible with
Carel Slave set on pLAN serial
WinLoad remote, GSM modem X Can only be activated on one serial port.
PlantVisor remote, GSM modem X GSM
Send and receive SMS X
Incompatible with the protocol PSTN; if activated on BMS serial is incompatible with
Carel Slave set on pLAN serial
Belimo devices X MP-Bus
Maximum of 8 devices
Serial printer X Serial printer
75
serial 0 -
pLAN serial 1 - BMS
serial 2 -
FieldBus

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carel pCO3 series and is the answer not in the manual?

Carel pCO3 series Specifications

General IconGeneral
Protection RatingIP20
Communication PortsRS-485
DisplayGraphic LCD with backlight
Power Supply24 Vac/dc ±10%
Storage Temperature+70°C
Humidity10% to 90% non-condensing