EasyManua.ls Logo

Carel pRack pR300 - 3. CONFIGURATION PROCEDURE

Carel pRack pR300
16 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
+030220735 - 1.0 - 19.05.2016
ENG
3. CONFIGURATION PROCEDURE
To configure a driver, proceed as follows:
1. for a new installation, complete the pRack configuration using the Wizard, making sure to specify that
the driver is used
pR300T
Booster system
pR300
Cascade system
pR300
Pumped system
2. connect the driver to port J26 and make sure that the address corresponds to the value set on pRack
(default 198)
3. on screen Id03, download the configuration by selecting “Download EVD settings”
Restore EVD defaults:
NO
Download EVD settings:
NO
Defaults EVD Id03
4. switch the pRack controller off and on again
If replacing the driver, check compatibility between the pRack and EVD EVO versions, as shown in
paragraph 2, then complete the configuration procedure starting from point 2.