pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index Display description Description Default UOM Values
Aa62
(display only)
Status,curr. Eff ective status of screw compressor 2 --- --- Off
Start up
Stage1
Stage 2
Stage 3
Stage 4
Status, req. Status required for the screw compressor 2 --- --- Off
Start up
Stage1
Stage 2
Stage 3
Stage 4
Minimum on time Countdown for minimum on time screw comp. 2 --- s 0…999
Min.off /starts Countdown for minim. off time or wait between successive starts screw comp. 2 --- s 0…999
Next step Countdown for next step activation screw comp. 2 --- s 0…999
Aa70
(display only)
Zone Envelope zone for screw compressor 1 --- --- 0…14
Max admit.time Maximum duration allowed in the zone min 0…999
Countdown Countdown s 0…32000
Max admit.power Maximum capacity allowed in the zone % 0…100
Aa71
(display only)
Startup status Start-up status for screw compressor 1 --- --- Off
Compressor on
Intermediate interval
Final interval
Compressor off
Restart Alarm
N° startup restart Number of restarts --- --- 0…99
Aa72
(display only)
Err.code Type of error in envelope defi nition --- --- No error / Env. def. inconsist..
Al.code Type of alarm activated --- --- No Alarm
Max time elapsed
Zone not allowed
Max. no. of restarts
Envel.def.error code Type of error in selection of predefi ned envelope --- --- No error
Comp. not supported
Gas type not allowed
Aaan
(display only)
Reg.var. Control variable value for generic stage function 1 --- … … (**)
Enable Enabling variable status for generic stage function 1 --- --- Not active
active
Setpoint Control set point for generic stage function 1 --- … … (**)
Diff erential Control diff erential for generic stage function 1 --- … … (**)
Mode Control mode for generic stage function 1 (direct or reverse) --- --- D, R
Status Status of generic stage function 1 --- --- Not active / Active
…… … ………
Aaar
(display only)
Reg.var. Control variable value for the generic stage function 5 --- … … (**)
Enable Enabling variable status for the generic stage function 5 --- --- Not active / Active
Setpoint Control set point for the generic stage function 5 --- … … (**)
Diff erential Control diff erential for the generic stage function 5 --- … … (**)
Mode Control mode for the generic stage function 5 (direct or reverse) --- --- D, R
Status Status of generic stage function 5 --- --- Not active / Active
Aaas
(display only)
Reg.variable Control variable value for generic modulating function 1 --- … … (**)
Enable Enabling variable status for generic modulating function 1 --- --- Not active / Active
Setpoint Control set point for generic modulating function 1 --- … … (**)
Diff erential Control diff erential for generic modulating function 1 --- … … (**)
Mode Control mode for generic modulating function 1 (direct or reverse) --- --- D, R
Status Status of generic modulating function 1 --- % 0.0…100.0
Aaat
(display only)
Reg.variable Control variable value for generic modulating function 2 --- … … (**)
Enable Enabling variable status for generic modulating function 2 --- --- Not active / Active
Setpoint Control set point for generic modulating function 2 --- … … (**)
Diff erential Control diff erential for generic modulating function 2 --- … … (**)
Mode Control mode for generic modulating function 2 (direct or reverse) --- --- D, R
Status Status of generic modulating function 2 --- % 0.0…100.0
Aaau
(display only)
Reg.variable Control variable status for generic alarm function 1 --- --- Not active / Active
Enable Enabling variable status for generic alarm function 1 --- --- Not active / Active
Type Type of alarm for generic alarm function 1 --- --- Light / Serious
Delay time Control diff erential for generic alarm function 1 --- s 0…9999
Status Status of generic alarm function 1 --- --- Not active / Active
Aaav
(display only)
Reg.variable Control variable status for generic alarm function 2 --- --- Not active / Active
Enable Enabling variable status for generic alarm function 2 --- --- Not active / Active
Type Type of alarm for generic alarm function 2 --- --- Light / Serious
Delay time Control diff erential for generic alarm function 2 --- s 0…9999
Status Status of generic alarm function 2 --- --- Not active / Active
Aaaw
(display only)
Weekday Day of the week --- --- Monday, …, Sunday
TB1: --:-- -> --:-- Enabling and defi nition of time band 1: start hour and minutes, end hour and
minutes for the generic scheduling function
--- … …
…… ………
TB4: --:-- -> --:-- Enabling and defi nition of time band 4: start hour and minutes, end hour and
minutes for the generic scheduling function
--- … …
Status Status of generic scheduling function --- --- Not active / Active
Aaax
(display only)
Status Status of heat recovery function (line 1) --- --- OFF / ON
Heat recl. temp. Heat recovery temperature (line 1) --- … … (**)
An.OUT modulat. Status of modulating heat recovery valve output (line 1) --- --- 0.0…100.0
HR Prevent Status of prevention via heat recovery (line 1) --- --- OFF / ON
Aaay
(display only)
Status Status of heat recovery function (line 2) --- --- OFF / ON
Heat recl. temp. Heat recovery temperature (line 2) --- … … (**)
An.OUT modulat. Status of modulating heat recovery valve output (line 2) --- --- 0.0…100.0
HR Prevent Status of prevention via heat recovery (line 2) --- --- OFF / ON
Aaaz
(display only)
Status Status of ChillBooster device (line 1) --- --- OFF / ON
Ext.temp. Outside temperature (line 1) --- … … (**)
Ext.temp.thr. ChillBooster activation threshold (line 1) --- … … (**)
Time fan 100% Number of minutes elapsed with fans at 100/number of min. allowed (line 1) --- min 0…999/0…999
Aaa1
(display only)
Status Status of ChillBooster device (line 2) --- --- OFF / ON
Ext.temp. Outside temperature (line 2) --- … … (**)
Ext.temp.thr. ChillBooster activation threshold (line 2) --- … … (**)
Time fan 100% Number of minutes elapsed with fans at 100/number of minutes allowed
(line 1)
--- min 0…999/0…999