pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index Display description Description Default UOM Values
Aaa2
(display only)
Cond.temp. Saturated condensing temperature (line 1) --- … … (**)
Liquid Temp. Liquid temperature (line 1) --- … … (**)
Subcooling Subcooling (line 1) --- … … (**)
Status Status of subcooling function (line 1) --- --- Open / Closed
Aaa4 (display
only)
Action 1
Description and status of the reduced power consumption action associated
with the fi rst digital input from pLoads (line 1)
--- --- OFF / ON
Action 2
Description and status of the reduced power consumption action associated
with the second digital input from pLoads (line 1)
--- --- OFF / ON
Aaa5 (display
only)
Action 1
Description and status of the reduced power consumption action associated
with the fi rst digital input from pLoads (line 2)
--- --- OFF / ON
Action 2
Description and status of the reduced power consumption action associated
with the second digital input from pLoads (line 2)
--- --- OFF / ON
Aaa6 (display
only)
Current Value read by the current sensor (line 1) --- A 0 to 999.9
Inst. power Instant power calculated (line 1) --- kW 0 to 100
Power today Power consumption during the current day (line 1) --- kWh 0 to 32767
Previous Power consumption during the previous day (line 1) --- kWh 0 to 32767
Ab01
(display only)
User setp. User-defi ned set point for suction pressure control, proportional control
(line 1)
--- … … (**)
Actual.setpoint Eff ective set point for suction pressure control, proportional control (with
compensation applied, line 1)
--- … … (**)
Diff . Suction pressure control diff erential, proportional control (line 1) --- … … (**)
Ab02
(display only)
User setp. User-defi ned set point for suction pressure control, proportional control
(line 1)
--- … … (**)
Actual.setpoint Eff ective set point for suction pressure control, proportional control (with
compensation applied, line 1)
--- … … (**)
Neutral zone Neutral zone for suction pressure control (line 1) --- … … (**)
Incr.diff . Increase diff erential for suction pressure control, neutral zone control (line 1) --- … … (**)
Decr.diff . Decrease diff erential for suction pressure control, neutral zone control
(line 1)
--- … … (**)
Ab03
(display only)
User setp. User-defi ned set point for suction pressure control, proportional control
(line 2)
--- … … (**)
Actual.setp. Eff ective set point for suction pressure control, proportional control (with
compensation applied, line 2)
--- … … (**)
Diff . Suction pressure control diff erential, proportional control (line 2) --- … … (**)
Ab04
(display only)
User setp. User-defi ned set point for suction pressure control, proportional control
(line 2)
--- … … (**)
Actual.setp. Eff ective set point for suction pressure control, proportional control (with
compensation applied, line 2)
--- … … (**)
Neutral zone Neutral zone for suction pressure control (line 2) --- … … (**)
Incr.diff . Increase diff erential for suction pressure control, neutral zone control (line 2) --- … … (**)
Decr.diff . Decrease diff erential for suction pressure control, neutral zone control (line 2) --- … … (**)
Ab05
(display only)
User setp. User-defi ned set point for condensing pressure control, proportional control
(line 1)
--- … … (**)
Actual.setp. Eff ective set point for condensing pressure control, proportional control
(with compensation applied, line 1)
--- … … (**)
Diff . Condensing pressure control diff erential, proportional control (line 1) --- … … (**)
Ab06
(display only)
User setp. User-defi ned set point for condensing pressure control, proportional control
(line 1)
--- … … (**)
Actual.setp. Eff ective set point for condensing pressure control, proportional control
(with compensation applied, line 1)
--- … … (**)
Neutral zone Neutral zone for condensing pressure control (line 1) --- … … (**)
Incr.diff . Increase diff erential for the condensing pressure control, neutral zone control
(line 1)
--- … … (**)
Decr.diff . Decrease diff erential for the condensing pressure control, neutral zone
control (line 1)
--- … … (**)
Ab07
(display only)
User setp. User-defi ned set point for condensing pressure control, proportional control
(line 2)
--- … … (**)
Actual.setp. Eff ective set point for condensing pressure control, proportional control
(with compensation applied, line 2)
--- … … (**)
Diff . Condensing pressure control diff erential, proportional control
(line 2)
--- … … (**)
Ab08
(display only)
User setp. User-defi ned set point for condensing pressure control, proportional control
(line 2)
--- … … (**)
Actual setp. Eff ective set point for condensing pressure control, proportional control
(with compensation applied, line 2)
--- … … (**)
Neutral zone Neutral zone for condensing pressure control (line 2) --- … … (**)
Incr.diff . Increase diff erential for the condensing pressure control, neutral zone control
(line 2)
--- … … (**)
Decr.diff . Decrease diff erential for the condensing pressure control, neutral zone
control (line 2)
--- … … (**)
Ab12
Setpoint Setpoint without compensation (suction line 1) 3,5 barg … … (**)
Ab13
Setpoint Setpoint without compensation (condenser line 1) 12,0 barg … … (**)
Ab14
Setpoint Setpoint without compensation (suction line 2) 3,5 barg … … (**)
Ab15
Setpoint Setpoint without compensation (condenser line 2) 12,0 barg … … (**)
Ac01
Status Unit status (display only) Off from
keypad
--- Waiting..
Unit On/
Off from alarm
Off from
blackout
Off from BMS
Off by default
Off by DIN
Off from
keypad
Manual op.
Prevent HP
--- On-Off from keypad (line 1) OFF --- OFF / ON