56
ENG
pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index Display description Description Default UOM Values
Ac02
L1:
L2:
Unit status (display only) Off from
keypad
--- …(See above Ac01)
--- On-Off from keypad (line 1) OFF --- OFF / ON
--- On-Off from keypad (line 2) OFF --- OFF / ON
Ac03
Enable of unit OnOff
By digit input
Enable unit On/Off from digit input (line 1) NO --- NO / YES
By supervisor Enable unit On/Off from supervisor (line 1) NO --- NO / YES
By black out Enable unit On/Off from black out (line 1) NO --- NO / YES
Ac04
Unit on delay after
blackout
System on delay after black out (line 1) 0 s 0…999
Ac06
Enable of unit OnOff
By digit input
Enable unit On/Off from digit input (line 2) NO --- NO / YES
By supervisor Enable unit On/Off from supervisor (line 2) NO --- NO / YES
By black out Enable unit On/Off from black out (line 2) NO --- NO / YES
Ac07
Unit on delay after
blackout
System on delay after black out (line 2) 0 s 0…999
Mask index Display Description Description Default UOM Values
B.Input./output (the I/Os available depend on the selected confi guration, the following are just some examples. For the complete list of I/O positions availa-
ble see Appendix A.5)
Baa02
DI Alarm 1 for compressor 1 DI position (line 1) 03 --- ---, 01…18, B1…B10 (****)
Status (display only) Status of alarm 1 for compressor 1 DI (line 1) --- --- Closed
Open
Logic Logic of alarm 1 for compressor 1 DI (line 1) NC --- NC / NO
Function (display only) Alarm 1 for compressor 1 function status (line 1) --- --- Not active / Active
…… … ………
Bab01
--- Suction pressure probe position (line1) B1 --- ---, B1…B10 (****)
--- Suct pressure probe type (line 1) 4-20mA --- ----
0-1V - 0-10V- 4-20mA- 0-5V
--- (display only) Suction pressure value (line 1) --- … … (**)
Upper value Suct pressure maximum value (line 1) 7,0 barg … … (**)
Lower value Suct pressure minimum value (line 1) -0,5 barg … … (**)
Calibration Suction pressure probe adjustment (line 1) 0.0 barg … … (**)
…… … ………
Bac02
Line relay DO Compressor 1 line DO position and status (On/Off ) display (line 1) … --- ---, 01…29 (****)
Part winding DO/Star
relay DO (*)
Compressor 1 part winding or star DO position and status (On/Off )
display (line 1)
… --- ---, 01…29 (****)
---/ Delta relay DO (*) Compressor 1 delta DO position and status (On/Off ) display (line 1) … --- ---, 01…29 (****)
Logic DO logic to start compressor 1 (line 1) NC --- NC / NO
Bac03
DO Compressor 1 unloader 1 DO position (line 1) … --- ---, 01…29 (****)
Status (display only) Status for compressor 1 unloader 1 DO (line 1) --- --- Closed / Open
Logic Logic for compressor 1 unloader 1 DO (line 1) NO --- NC / NO
Function (display only) Compressor 1 unloader 1 function status (line 1) --- --- Not active / Active
…… … ………
Bad01
AO Compressor modulating device AO position (line 1) 0 --- ---, 01…06 (****)
Type (****)
Type of output, PWM / phase control for compressor modulating device
(line 1)
FCS1*-CON-
VONOFF
---
----
FCS1*-CONVONOFF
FCS3*-CONV010"
Status (display only) Modulating device output value (line 1) 0 % 0.0 to 100.0
…… … ………
Bb01
Suction L1 Suction line 1 in manual mode DIS --- DIS / EN
Suction L2 Suction line 2 in manual mode DIS --- DIS / EN
Discharge L1 Condenser line 1 in manual mode DIS --- DIS / EN
Discharge L2 Condenser line 2 in manual mode DIS --- DIS / EN
Timeout Manual mode duration after last key pressed 10 min 0…500
Bba02
Compressor 1
Force to
Manual stages request for compressor 1 (line 1) OFF --- OFF / ON
2 STAGES (*)
3 STAGES (*)
4 STAGES (*)
…… … ………
Bba16
Compressor 12
Force to
Manual stage request for compressor 12 (line 1) OFF --- OFF / ON
2 STAGES (*)
3 STAGES (*)
4 STAGES (*)
Bba17
Oil cool pump1
Force to
Manual operating status for oil cooling pump 1 (line 1) OFF --- OFF / ON
Oil cool pump2
Force to
Manual operating status for oil cooling pump 2 (line 1) OFF --- OFF / ON
Bba18
Oil cool fan
Force to
Manual operating status for oil cooling fan (line 1) OFF --- OFF / ON
Bba20
Compressor 1
Force to
Manual stage request for compressor 1 (line 2) OFF --- OFF / ON
2 STAGES (*)
3 STAGES (*)
4 STAGES (*)
…… ………
Bba34
Compressor 12
Force to
Manual stage request for compressor 12 (line 2) OFF --- OFF / ON
2 STAGES (*)
3 STAGES (*)
4 STAGES (*)
Bba35
Oil cool pump1
Force to
Manual operating status for oil cooling pump 1 (line 2) OFF --- OFF / ON
Oil cool pump2
Force to
Manual operating status for oil cooling pump 2 (line 2) OFF --- OFF / ON
Bba37
Oil cool fan
Force to
Manual operating status for oil cooling fan (line 2) OFF --- OFF / ON
Bba38
Fan1
force
Manual operating status for fan 1 (line 1) OFF --- OFF / ON
…… … ………
Bba53
Fan16
force
Manual operating status for fan 16 (line 1) OFF --- OFF / ON