Mask index Display description Description Default UOM Values
Efa09
High alarm High alarm enabling for generic stage function 1 DISAB. --- DISABLE / ENABLE
High alarm High alarm threshold for generic stage function 1 0.0 °C … (**)
Delay time High alarm delay for generic stage function 1 0 s 0…9999
Alarm type Low alarm enabling for generic stage function 1 LIGHT --- LIGHT / SERIOUS
Low alarm Low alarm threshold for generic stage function 1 DISAB. --- DISABLE / ENABLE
Low alarm Low alarm delay for generic stage function 1 0.0 °C … (**)
Delay time Low alarm delay for generic stage function 1 0 s 0…9999
Alarm type Type of low alarm for generic stage function 1 LIGHT --- LIGHT / SERIOUS
……
Efb05
Gen.Modulat.1 Enable generic modulating function 1 management DISAB. --- DISABLE / ENABLE
Gen.Modulat.2 Enable generic modulating function 2 management DISAB. --- DISABLE / ENABLE
Efb06
Regulation variable Control variable for generic modulating function 1 --- ---
Mode Direct or reverse modulation DIRECT --- DIRECT / REVERSE
Efb07
Enable Enabling variable for generic modulating function 1 --- ---
Description Enable description change SKIP --- SKIP / CHANGE
--------------- Description --- ---
Efb08
Setpoint Setpoint for generic modulating function 1 0.0 °C … (**)
Diff erential Diff erential for generic modulating function 1 0.0 °C … (**)
Efb09
High alarm High alarm enabling for generic modulating function 1 DISAB. --- DISABLE / ENABLE
High alarm High alarm threshold for generic modulating function 1 0.0 °C … (**)
Delay time High alarm delay for generic modulating function 1 0 s 0…9999
Alarm type Low alarm enabling for generic modulating function 1 LIGHT --- LIGHT / SERIOUS
Efb010
Out upper limit Output upper limit for generic modulating function 1 100.0 % 0…100
Out lower limit Output lower limit for generic modulating function 1 0.0 % 0…100
Enable cutoff Enable cut off function for generic modulating function 1 NO --- NO / YES
Cutoff diff . Cut off diff erential for generic modulating function 1 0.0 °C … (**)
Cutoff hys. Cut off hysteresis for generic modulating function 1 0.0 °C … (**)
Efb20
Low alarm Low alarm enabling for generic modulating function 1 DISAB. --- DISABLE / ENABLE
Low alarm Low alarm threshold for generic modulating function 1 0.0 °C … (**)
Delay time Low alarm delay for generic modulating function 1 0 s 0…9999
Alarm type Low alarm type for generic modulating function 1 LIGHT --- LIGHT / SERIOUS
……
Efc05
Gen.alarm 1 Enable generic alarm function 1 management DISAB. --- DISABLE / ENABLE
Gen.alarm 2 Enable generic alarm function 2 management DISAB. --- DISABLE / ENABLE
Efc06
Regulation variable Monitored variable for generic alarm function 1 --- ---
Enable Enabling variable for generic alarm function 1 --- ---
Description Enable description change SKIP --- SKIP / CHANGE
--------------- Description --- ---
Efc07
Alarm type Alarm type for generic alarm function 1 LIGHT --- LIGHT / SERIOUS
Delay time Delay for generic alarm function 1 0 s 0…9999
……
Efd05
Generic Function Sche-
duler
Enable generic scheduler function DISAB. --- DISABLE / ENABLE
Gen.funct.scheduling
connected to global
scheduling
Generic scheduler function considers the same special days and periods
of global scheduler
NO --- NO / YES
Efd06 Enable Enabling variable for generic scheduler function --- ---
Efd07
Activ.Time Bands Day of the week --- --- MON, ..., SUN
TB1: --:-- -> --:-- Time band 1 enabling and defi nition: start hour and minute, end hour
and minute (suction line 1)
---
……
TB4: --:-- -> --:-- Time band 4 enabling and defi nition: start hour and minute, end hour
and minute (suction line 1)
---
Changes Time band changes action --- --- ---
CONFIRM&SAVE
LOAD PREVIOUS
CLEAR ALL
Copy to Copy settings to other days 0 --- MONDAY…SUNDAY; MON-FRI;
MON-SAT; SAT&SUN; ALL DAYS
Efe05
Gen.A Measure Generic analogue input A unit of measure selection °C --- °C; °F; barg; psig; %; ppm -
……
Efe06/Efe07 (**)
--- Generic probe A position B1 --- ---, B1…B10 (****)
--- Generic probe A type 4-20mA --- … (**)
--- (display only) Generic probe A value --- … (**)
Upper value Generic probe A max. limit 30.0 barg … (**)
Lower value Generic probe A min. limit 0.0 barg … (**)
Calibration Generic probe A adjustment 0.0 barg … (**)
... ...
Efe16
DI Generic digital input F DI position --- --- ---, 01…18, B1…B10 (****)
Status (display only) Status of generic digital input F DI --- --- Closed / Open
Logic Logic of generic digital input F DI NC --- NC / NO
Function (display only) Status of generic digital input F DI --- --- Not active / Active
... ...
Efe21
DO Generic stage 1 DO position --- ---, 01…29 (****)
Status (display only) Status of generic stage 1 DO --- --- Closed / Open
Logic Logic of generic stage 1 DO NO --- NC / NO
Function (display only) Generic stage 1 DO function status --- --- Not active / Active
……
Efe29
Modulating.1 Generic modulating 1 AO position 0 --- ---, 01…06 (****)
Type (****)
Type of output, PWM / phase control for generic modulating function
1 AO (line 1)
FCS1*-CON-
VONOFF
---
FCS1*-CONVONOFF; "-----";"
MCHRTF*";" FCS3*-CONV010"
Status (display only) Generic modulating 1 output value 0 % 0.0…100.0
……
Egaa01
DI ChillBooster fault DI position (line 1) --- --- ---, 01…18, B1…B10 (****)
Status (display only) Status of ChillBooster fault DI (line 1) --- --- Closed / Open
Logic Logic of ChillBooster fault DI (line 1) NC --- NC / NO
Function (display only) Status of ChillBooster fault (line 1) --- --- Not active / Active