pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index Display description Description Default UOM Values
Egaa02
DO ChillBooster DO position (line 1) … --- ---, 01…29 (****)
Status (display only) Status of ChillBooster DO (line 1) --- --- Closed / Open
Logic Logic of ChillBooster DO (line 1) NO --- NC / NO
Function (display only) Status of ChillBooster function (line 1) --- --- Not active / Active
Egab01
Device present Enable ChillBooster function (line 1) NO --- NO / YES
Deactivation when fan-
spower falls under
Fan capacity under which ChillBooster is deactivated (line 1) 95 % 0…100
Egab02
Before the activation fans
at max for
Fans work at maximum capacity at least for this time before
ChillBooster activation (line 1)
5 min 0 to 300
Ext.Temp.Thr. Outside temperature threshold for ChillBooster activation (line 1) 30.0 °C … … (**)
Egab03
Sanitary proc. Enable hygiene procedure (line 1) Disab. --- DISABLE / ENABLE
start at Hygiene procedure starting time (line 1) 00:00 --- …
Duration Hygiene procedure duration (line 1) 0 min 0 to 30
Ext.temp.thr Outside temperature threshold for hygiene procedure activati. (line 1) 5,0 °C … … (**)
Egab04
ChillBooster requires
maintenance after
ChillBooster maximum running time (line 1) 200 h 0…999
Reset maintenance time ChillBooster maintenance time reset (line 1) NO --- NO / YES
Ehb01
Avoid simultaneous
pulses betw.lines
Enable simultaneous compressor start up inhibition NO --- NO / YES
Delay Delay between start up for compressors on diff erent lines 0 s 0…999
Ehb03
Force off L2 Comp.s for
line 1 fault
Enable line 2 compressor switch OFF due to line 1 compressor fault NO --- NO / YES
Delay Delay for line 2 compressor switch off after serious alarm on line 1
compressors
0 s 0…999
Ehb04
Switch on L1 Comp.s for
L2 activation
Enable line 1 compressor switch ON due to line 2 compressor
switch ON
NO --- NO / YES
Switch on period Delay for line1 compressor switch on for line 2 compressor switch on 30 s 0…999
Force off line 2 if line 1
is off
Enable line 2 compressor switch OFF due to line 1 switch OFF NO --- NO / YES
Ehb05
Enable min threshold for
L1 activation
Enable L1 activation by DSS only when suction pressure is greater than
a minimum threshold
NO --- NO / YES
Threshold Minimum threshold for line 1 activation by DSS --- … … (**)
Eia02
Setpoint SH PID control set point (valve 1) 11.0 K -40.0…180.0
LowSH thres. Low superheat protection threshold (valve 1) 5.0 K -40.0…180.0
LOP thresh. Low operating pressure protection threshold (valve 1) -50.0 --- -60.0… 200.0
MOP thresh. Maximum operating pressure protection threshold (valve 1) 50.0 --- -60.0… 200.0
Eia04
Setpoint SH PID control set point (valve 2) 11.0 K -40.0…180.0
LowSH thres. Low superheat protection threshold (valve 2) 5.0 K -40.0…180.0
LOP thresh. Low operating pressure protection threshold (valve 2) -50.0 --- -60.0… 200.0
MOP thresh. Maximum operating pressure protection threshold (valve 2) 50.0 --- -60.0… 200.0
Eib02
Enable manual
Valve position
Enable manual positioning (valve 1) NO NO/YES
Manual valve position: Manual position (valve 1) 0 --- Min / Max
Eib04
Enable manual
Valve position
Enable manual positioning (valve 2) NO NO/YES
Manual valve position: Manual position (valve 2) 0 --- Min / Max
Eic02
S1 off set Probe S1 reading off set (valve 1) 0.0 Barg/psig
S1 probe (display) Value read by probe S1 (valve 1) --- Barg/psig
S2 off set Probe S2 reading off set (valve 1) 0.0 °C/°F
S2 probe (display) Value read by probe S2 (valve 1) --- °C/°F
Eic03
S3 off set Probe S3 reading off set (valve 1) 0.0 Barg/psig
S3 probe (display) Value read by probe S3 (valve 1) --- Barg/psig
S4 off set Probe S4 reading off set (valve 1) 0.0 °C/°F
S4 probe (display) Value read by probe S4 (valve 1) --- °C/°F
Eic04
Alarm: Abilita l’allarme sonda S1 ( valvola 1 )
EN.
EN./DIS.
Type: Type of probe S1 (valve 1) 4-20mA
4-20mA / 4-20mA REMOTE /
4-20mA EXTERNAL / 0-5V RAT.
Min.: Minimum probe S1 reading (valve 1) -1.0 Barg/pisg -20.0...200.0
Max.: Maximum probe S1 reading (valve 1) 9.3 Barg/pisg -20.0...200.0
Alarm min.: Minimum probe S1 alarm threshold (valve 1) -1.0 Barg/pisg -20.0...200.0
Alarm max.: Maximum probe S1 alarm threshold (valve 1) 9.3 Barg/pisg -20.0...200.0
Eic05
Alarm: Enable probe S2 alarm (valve 1 )
EN. EN./DIS.
Type: Type of probe S2 (valve 1) CAREL NTC
CAREL NTC / 0-10V EXT. SI-
GNAL / NTC SPKP**T0 / CAREL
NTC-HT
Alarm min.: Minimum probe S2 alarm threshold (valve 1) -50.0 °C/°F -60.0...200.0
Alarm max.: Maximum probe S2 alarm threshold (valve 1) 105.0 °C/°F -60.0...200.0
Eic06
Alarm: Enable probe S3 alarm (valve 1)
EN. EN./DIS.
Type: Type of probe S3 (valve 1) 4-20mA
4-20mA / 4-20mA REMOTE /
4-20mA EXTERNAL / 0-5V RAT.
Min.: Minimum probe S3 reading (valve 1) -1.0 Barg/pisg -20.0...200.0
Max.: Maximum probe S3 reading (valve 1) 30.0 Barg/pisg -20.0...200.0
Alarm min.: Minimum probe S3 alarm threshold (valve 1) -1.0 Barg/pisg -20.0...200.0
Alarm max.: Maximum probe S3 alarm threshold (valve 1) 30.0 Barg/pisg -20.0...200.0
Eic07
Alarm: Enable probe S4 alarm (valve 1)
EN. EN./DIS.
Type: Type of probe S4 (valve 1) CAREL NTC
CAREL NTC / NTC SPKP**T0 /
CAREL NTC-HT
Alarm min.: Minimum probe S4 alarm threshold (valve 1) -50.0 °C/°F -60.0...200.0
Alarm max.: Maximum probe S4 alarm threshold (valve 1) 105.0 °C/°F -60.0...200.0