Mask index Display description Description Default UOM Values
Eic08
ID1 confi guration: Confi guration of action of digital input 1 on driver (valve 1) REG. BACKUP
DISABLED / REG. SAFETY / REG.
BACKUP / START/STOP REG. /
VALVE FORCED 100% OPEN /
BATTERY ALARM MNG. / VALVE
REGULATION OPT. AFTER
DEFROST
ID2 confi guration: Confi guration of action of digital input 2 on driver (valve 1) DISABLED
DISABLED / REG. SAFETY / REG.
BACKUP / START/STOP REG. /
VALVE FORCED 100% OPEN /
BATTERY ALARM MNG. / VALVE
REGULATION OPT. AFTER
DEFROST
Eic09
DI1: Digital input 1 status (valve 1) ---
DI2: Digital input 2 status (valve 1) ---
Eic10 Valve A relay confi g.: Confi guration of digital output1 (valve 1) ALARM RELAY
DISABLED / ALARM RELAY
/ SOLENOID VALVE RELAY /
VALVE + ALARM RELAY / RE-
VERSED ALARM RELAY / VALVE
POSITION RELAY
Eic11 Valve B relay confi g.: Confi guration of digital output 2 (valve 1) ALARM RELAY
DISABLED / ALARM RELAY
/ SOLENOID VALVE RELAY /
VALVE + ALARM RELAY / RE-
VERSED ALARM RELAY / VALVE
POSITION RELAY
Eic12
S1 off set Probe S1 reading off set (valve 2) 0.0 Barg/psig
S1 probe (display) Value read by probe S1 (valve 2) --- Barg/psig
S2 off set Probe S2 reading off set (valve 2) 0.0 °C/°F
S2 probe (display) Value read by probe S2 (valve 2) --- °C/°F
Eic13
S3 off set Probe S3 reading off set (valve 2) 0.0 Barg/psig
S3 probe (display) Value read by probe S3 (valve 2) --- Barg/psig
S4 off set Probe S4 reading off set (valve 2) 0.0 °C/°F
S4 probe (display) Value read by probe S4 (valve 2) --- °C/°F
Eic14
Alarm: Enable probe S1 alarm (valve 2)
EN. EN./DIS.
Type: Type of probe S1 (valve 2) 4-20mA
4-20mA / 4-20mA REMOTE /
4-20mA EXTERNAL / 0-5V RAT.
Min.: Minimum probe S1 reading (valve 2) -1.0 Barg/pisg -20.0...200.0
Max.: Maximum probe S1 reading (valve 2) 9.3 Barg/pisg -20.0...200.0
Alarm min.: Minimum probe S1 alarm threshold (valve 2) -1.0 Barg/pisg -20.0...200.0
Alarm max.: Maximum probe S1 alarm threshold (valve 2) 9.3 Barg/pisg -20.0...200.0
Eic15
Alarm: Enable probe S2 alarm (valve 2)
EN. EN./DIS.
Type: Type of probe S2 (valve 2) CAREL NTC
CAREL NTC / 0-10V EXT. SI-
GNAL / NTC SPKP**T0 / CAREL
NTC-HT
Alarm min.: Minimum probe S2 alarm threshold (valve 2) -50.0 °C/°F -60.0...200.0
Alarm max.: Maximum probe S2 alarm threshold (valve 2) 105.0 °C/°F -60.0...200.0
Eic16
Alarm: Enable probe S3 alarm (valve 2)
EN. EN./DIS.
Type: Type of probe S3 (valve 2) 4-20mA
4-20mA / 4-20mA REMOTE /
4-20mA EXTERNAL / 0-5V RAT.
Min.: Minimum probe S3 reading (valve 2) -1.0 Barg/pisg -20.0...200.0
Max.: Maximum probe S3 reading (valve 2) 30.0 Barg/pisg -20.0...200.0
Alarm min.: Minimum probe S3 alarm threshold (valve 2) -1.0 Barg/pisg -20.0...200.0
Alarm max.: Maximum probe S3 alarm threshold (valve 2) 30.0 Barg/pisg -20.0...200.0
Eic17
Alarm: Enable probe S4 alarm (valve 2)
EN. EN./DIS.
Type: Type of probe S4 (valve 2) CAREL NTC
CAREL NTC / NTC SPKP**T0 /
CAREL NTC-HT
Alarm min.: Minimum probe S4 alarm threshold (valve 2) -50.0 °C/°F -60.0...200.0
Alarm max.: Maximum probe S4 alarm threshold (valve 2) 105.0 °C/°F -60.0...200.0
Eic18 ID1 confi guration: Confi guration of action of digital input 1 on driver (valve 2) REG. BACKUP
DISABLED / REG. SAFETY / REG.
BACKUP / START/STOP REG. /
VALVE FORCED 100% OPEN /
BATTERY ALARM MNG. / VALVE
REGULATION OPT. AFTER
DEFROST
ID2 confi guration: Confi guration of action of digital input 2 on driver (valve 2) DISABLED
DISABLED / REG. SAFETY / REG.
BACKUP / START/STOP REG. /
VALVE FORCED 100% OPEN /
BATTERY ALARM MNG. / VALVE
REGULATION OPT. AFTER
DEFROST
Eic19
DI1: Digital input 1 status (valve 2) ---
DI2: Digital input 2 status (valve 2) ---
Eic20 Valve A relay confi g.: Confi guration of digital output1 (valve 2) ALARM RELAY
DISABLED / ALARM RELAY
/ SOLENOID VALVE RELAY /
VALVE + ALARM RELAY / RE-
VERSED ALARM RELAY / VALVE
POSITION RELAY
Eic21 Valve B relay confi g.: Confi guration of digital output 2 (valve 2) ALARM RELAY
DISABLED / ALARM RELAY
/ SOLENOID VALVE RELAY /
VALVE + ALARM RELAY / RE-
VERSED ALARM RELAY / VALVE
POSITION RELAY
Eid02
Valve A opening at
start-up
Valve opening at start of control (valve 1) 50 % 0…100
Eid04
Valve A opened in
stand-by
Enable valve opening with control not active (valve 1) NO NO/YES
Start-up delay after
defrost
Start control delay after defrost (valve 1) 10 min 0…60
Valve A preposit. delay Stationary time when valve pre-positions (valve 1) 6 s 0…18000