69
ENG
pRack +0300025EN rel. 1.3 - 17.12.2015
Mask index Display description Description Default UOM Values
Eid06
Prop Gain: Control proportional gain (valve 1) 15.0 0.0…800.0
Integral time: Control integral time (valve 1) 150 s 0…1000
Derivat.time: Control derivative time (valve 1) 5.0 s 0…1000
Eid08
LowSH protect.: Integral time with low superheat protection (valve 1) 10.0 s 0.0…800.0
LOP protection: Integral time with low operating pressure protection (valve 1) 10.0 s 0.0…800.0
MOP protection: Integral time with maximum operating pressure protection (valve 1) 20.0 s 0.0…800.0
Eid10
Threshold: High condensing temperature protection activation threshold (valve 1) 30.0 °C/°F -60.0…200.0
Integr.time: Integral time with high condensing temperature protection (valve 1) 0.5 s 0.0…800.0
Alarm timeout High condensing temperature alarm delay (valve 1) 600 s 0…18000
Eid11
LowSH: Low superheat alarm delay (valve 1) 300 s 0…18000
LOP: Low operating pressure alarm delay (valve 1) 300 s 0…18000
MOP: Maximum operating pressure alarm delay (valve 1) 600 s 0…18000
Eid13
Threshold Low suction temperature protection threshold (valve 1) -50.0 °C/°F -60.0…200.0
Timeout Low suction temperature alarm delay (valve 1) 300 s 0…18000
Eid15
Valve A opening at
start-up
Valve opening at start of control (valve 2) 50 % 0…100
Eid17
Valve A opened in
stand-by
Enable valve opening with control not active (valve 2) NO NO/YES
Start-up delay after
defrost
Start control delay after defrost (valve 2) 10 min 0…60
Valve A preposit. delay Stationary time when valve pre-positions (valve 2) 6 s 0…18000
Eid19
Prop Gain: Control proportional gain (valve 2) 15.0 0.0…800.0
Integral time: Control integral time (valve 2) 150 s 0…1000
Derivat.time: Control derivative time (valve 2) 5.0 s 0…1000
Eid21
LowSH protect.: Integral time with low superheat protection (valve 2) 10.0 s 0.0…800.0
LOP protection: Integral time with low operating pressure protection (valve 2) 10.0 s 0.0…800.0
MOP protection: Integral time with maximum operating pressure protection (valve 2) 20.0 s 0.0…800.0
Eid23
Threshold: High condensing temperature protection activation threshold (valve 2) 30.0 °C/°F -60.0…200.0
Integr.time: Integral time with high condensing temperature protection (valve 2) 0.5 s 0.0…800.0
Alarm timeout High condensing temperature alarm delay (valve 2) 600 s 0…18000
Eid24
LowSH: Low superheat alarm delay (valve 2) 300 s 0…18000
LOP: Low operating pressure alarm delay (valve 2) 300 s 0…18000
MOP: Maximum operating pressure alarm delay (valve 2) 600 s 0…18000
Eid26
Threshold Low suction temperature protection threshold (valve 2) -50.0 °C/°F -60.0…200.0
Timeout Low suction temperature alarm delay (valve 2) 300 s 0…18000
Eie02
Min.steps Minimum step confi guration, valve 1 50 0…9999
Max.steps Maximum step confi guration, valve 1 480 0…9999
Closing steps Closing step confi guration, valve 1 500 0…9999
Eie04
Min.steps Minimum step confi guration, valve 2 50 0…9999
Max.steps Maximum step confi guration, valve 2 480 0…9999
Closing steps Closing step confi guration, valve 2 500 0…9999
Eif01
Enable EVD in PLB x Enable the EVD management on current board NO NO/YES
EVD valves number Number of drivers managed 1 1 / 2
EVS 1 Address Serial address of driver 1 198 0…207
EVS 2 Address
Serial address of driver 2 199 0…207
Eif02
Defaults: Run driver parameter setting procedure NO
Force Parameters: Override driver parameter settings NO
Regulation based on: Select cooling capacity used for control LINE 1 COMP LINE 1 COMP. / LINE 2 COMP
Eif03 Valve: Type of valve connected to the driver CAREL EXV
USER DEFINED / CAREL EXV
/ ALCO EX4 / ALCO EX5 /
ALCO EX6 / ALCO EX7 /
ALCO EX8 CAREL RECOM-
MENDED / ALCO EX8 ALCO
SPECIFICATION / SPORLAN SEI
0.5-11 / SPORLAN SER 1.5-20
/ SPORLAN SEI 30 / SPORLAN
SEI 50 / SPORLAN SEH 100 /
SPORLAN SEH 175 / Danfoss
ETS 12.5-25B / Danfoss ETS 50B
/ Danfoss ETS 100B / Danfoss
ETS 250 / Danfoss ETS 400 /
TWO CAREL EXV TOGETHER /
SPORLAN SER(I) G, J, K / Dan-
foss CCM 10-20-30 / Danfoss
CCM 40
Eif05
Main Regulation: Main control for the valve, for details refer to manual +0300005EN
R404 CON-
DENSER FOR
SUBCRITICAL
CO2
Possible control functions in
manual +0300005EN
Auxiliary regulation: Safety or auxiliary control
INVERSE HIGH
CONDENS.
TEMP.
PROTECTION
ON S3
Possible control functions in
manual +0300005EN
Eif06 Auxiliary refrigerant:
Refrigerant used for P -> T conversion of probe S3 with high condensing
temperature protection
R744
Eif09
S1 probe alarm manag: Type of action in the event of probe S1 fault
VALVE AT
FIXED POS.
NO ACTION / VALVE FORCE
CLOSED / VALVE AT FIXED POS
/ USE BACKUP S3
S2 probe alarm manag: Type of action in the event of probe S2 fault
VALVE AT
FIXED POS.
NO ACTION / VALVE FORCE
CLOSED / VALVE AT FIXED POS
/ USE BACKUP S4
Eif11 DC power supply Confi gure the type of power supply used for the driver NO NO / YES