25
NOTES:
1. Units are suitable for use on electrical systems where voltage sup-
plied to the unit is between the listed minimum and maximum limits.
2. Maximum allowable phase imbalance is 2% for voltage and 10%
for current.
Table 5 — 09FC Electrical Data
UNIT SIZE
POWER SUPPLY FAN MOTORS
MCA MOCP
REC FUSE
SIZE
VOLTAGE HZ
SUPPLY VOLTAGE
QTY
FLA
(EACH)
MIN MAX
020
208/230
60
187 253
4
10.6 45.1 50 50
380 342 418 5.8 24.7 30 30
400 360 400 5.5 23.4 25 2
5
460 414 506 4.8 20.4 25 25
575 518 633 3.8 16.2 20 20
380
50
342 418 5.9 25.1 30 30
400 360 440 5.6 23.9 25 25
415 374 456 5.4 23.0 25 25
440 396 480 5.1 21.7 25 25
030
208/230
60
187 253
6
10.6 66.3 70 70
380 342 418 5.8 36.3 40 40
400 360 400 5.5 34.4 35 35
460 414 506 4.8 30.0 35 35
575 518 633 3.8 23.8 25 25
380
50
342 418 5.9 37.0 40 40
400 360 440 5.6 35.1 40 40
415 374 456 5.4 33.9 35 35
440 396 480 5.1 31.9 35 35
040
208/230
60
187 253
8
10.6 87.5 90 90
380 342 418 5.8 47.9 50 50
400 360 400 5.5 45.5 50 50
460 414 506 4.8 3
9.6 40 40
575 518 633 3.8 31.4 35 35
380
50
342 418 5.9 48.8 50 50
400 360 440 5.6 46.4 50 50
415 374 456 5.4 44.7 50 50
440 396 480 5.1 42.2 45 45
050
380
60
342 418
10
5.8 59.5 60 60
400 360 400 5.5 56.5 60 60
460 414 506 4.8 49.2 50 50
575 518 633 3.8 39.0 40 40
380
50
342 418 5.9 60.6 70 70
400 360 440 5.6 57.6 60 60
415 374 456 5.4 55.5 60 60
440 396 480 5.1 52.4 60 60
060
380
60
342 418
12
5.8 71.1 80 80
400 360 400 5.5 67.5 70 70
460 414 506 4.8 58.8 60 60
575 518 633 3.8 46.6 50 50
380
50
342 418 5.9 72.5 80 80
400 360 440 5.6 6
8.8 70 70
415 374 456 5.4 66.4 70 70
440 396 480 5.1 62.6 70 70
070
380
60
342 418
14
5.8 82.7 90 90
400 360 400 5.5 78.5 80 80
460 414 506 4.8 68.4 70 70
575 518 633 3.8 54.2 60 60
380
50
342 418 5.9 84.3 90 90
400 360 440 5.6 80.1 90 80
415 374 456 5.4 77.2 80 80
440 396 480 5.1 72.8 80 80
080
380
60
342 418
16
5.8 94.3 100 100
400 360 400 5.5 89.5 90 90
460 414 506 4.8 78.0 80 80
575 518 633 3.8 61.8 70 70
380
50
342 418 5.9 96.1 100 100
400 360 440 5.6 91.3 100 100
415 374 456 5.4 88.0 90 90
440 396 480 5.1 83.0 90 90
LEGEND
FLA Full Load Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection

Table of Contents