Communication - BACnet
See Table 15 for a list of BACnet Points.
Addressing the controller may be done with or without power.
Each time power is applied the controller reads the address.
Address is set using rotary switches. Set the Tens (10’s) switch to
the tens digit of the address, and the Ones (1’s) switch to the ones
digit. See Fig. 39.
Example: If the controllers address is 25, point the arrow on the
Tens (10’s) switch to 2 and the arrow on the Ones (1’s) switch to 5.
The factory default setting is 00 and must be changed to success-
fully install BACnet communication.
See Table 16 for required BACnet configurations.
Fig. 39 — Addressing the Controller
p
Table 15 — BACnet Points
POINT NAME TYPE BACNET NAME OBJECT ID R/W RANGE DEFAULT
Fan VFD Speed Output BAV fanspeed 1001 R 0 - 100 %
Mixing Valve Postion BAV mixing_valve_pct 1002 R 0 - 100 %
Outdoor Air Temperature BAV oa_temp 1003 R °F
Entering Load Water Temp BAV ent_load_wtr_temp 1019 R °F
Leaving Load Water Temp BAV lvg_load_wtr_temp 1020 R °F
System Outdoor Air Temp BAV system_oat 1901 R/W -999
System Entering Load Water Temp BAV system_elwt 1910 R/W -999
System Leaving Load Water Temp BAV system_llwt 1912 R/W -999
System Control Setpoint BAV system_ctrl_stpt 1916 R/W -999
Chilled Water Setpoint BAV ctrl_stpt 2024 R °F
Chilled Water Supply Temp BAV ctrl_temp 2035 R °F
Chilled Water Supply Setpoint BAV chws_setpoint 3024 R/W 15 - 75 °F 44
Cooling Lockout Offset BAV oat_cl_lockout_offset 3027 R/W 1 - 10 °^F 3
Cooling Lockout Temperature BAV oat_cl_lockout 9002 R/W -20 - 80 °F 50
Power Fail Restart Delay BAV start_delay 9007 R/W 0 - 600 sec 20
Fan Minimum Speed BAV fan_min_speed 9009 R/W 0 - 100 % 20
System OAT Master BAV mstr_oa_temp 80001 R °F
Cool Enable BBV cl_enable 1011 R/W
0=Disable
1=Enable
1
Bypass Valve Position BBV vlv_pos 2001 R
0=Close
1=Open
Fan VFD Enable BBV fanenable 2004 R
0=Stop
1=Start
Occupancy Status BBV occ_status 2008 R
0=Unocc
1=Occ
Operating Mode BBV op_mode 2014 R
0=Bypass
1=Free Cool
Run Command BBV run_cmnd 2030 R
0=Stop
1=Start
Shutdown BBV shutdown 9001 R/W
0=Inactive
1=Active
0
BAS On / Off BMSV keypad_ovrde 1001 R/W
1=Inactive
2=Occupied
3=Unoccupied
1
Low Chilled Water Supply Temp BBV chws_lo_alarm 7021 R
0=Normal
1=Alarm
Non-Operational Component BBV nonop_comp_alarm 7023 R
0=Normal
1=Alarm
Reverse Load Water Flow BBV reverse_flow_alarm 7025 R
0=Normal
1=Alarm
Outdoor Air Temp Sensor BBV oat_fail 7029 R
0=Normal
1=Alarm
Outdoor Air Temperature BBV oat_alarm 7036 R
0=Normal
1=Alarm
Fan VFD Fail BBV fan_vfd_fail 7039 R
0=Normal
1=Alarm
Entering Load Water Temperature BBV elwt_alarm 7040 R
0=Normal
1=Alarm
Entering Load Water Temp Sensor BBV ent_lwt_fail 7041 R
0=Normal
1=Alarm
Leaving Load Water Temperature BBV llwt_alarm 7043 R
0=Normal
1=Alarm
Leaving Load Water Temp Sensor BBV lvg_lwt_fail 7044 R
0=Normal
1=Alarm
Equipment Alarm BBV equip_alarm 7048 R
0=Normal
1=Alarm