EasyManua.ls Logo

Carrier 09FC020 - Power Wiring

Carrier 09FC020
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
27
Fig. 29 — Typical Main Power Connections
POWER WIRING
All power wiring must comply with applicable local and national
codes. A fused disconnect is supplied in the control panel with an
external handle on all 09FC models.
General Wiring Notes:
1. The control circuit does NOT require a separate power
source. Control circuit power is obtained by a step-down
transformer from the main three-phase power supply. The
LVT (low voltage terminal) strip is provided for field-wired
control devices.
2. All field power enters the unit through a hole located in the
bottom of the control box shelf. Refer to Fig. 25 for field wir-
ing details. Refer to Fig. 5-11 for exact location of field power
entry. Be sure to seal entering power wire conduit per NEC
requirements.
3. Maximum field wire sizes allowed by lugs on fused discon-
nect are listed in Table 4.
4. Terminals for field power supply are suitable for copper con-
ductors. Insulation must be rated 75°C minimum.
Control power is obtained from the main power supply and does
NOT require a separate source. A toggle switch, SW1 (marked
LEGEND
AO Analog Output (0-10 Vdc)
ALMAlarm Relay
BO Digital Output (Relay, 1A Max)
BMS Building Management System
CBCircuit Breaker
EWTEntering Water Temperature
FUFuse
FMFan Motor
GNDGround
IN Thermistor or Dry Contact Input
LWTLeaving Water Temperature
OATOutdoor Air Temperature
R1CW Valve Relay
R2CCW Valve Relay
R3 FC Enable Relay
R4 VFD Enable Relay
SWSwitch
TBTerminal Block
TRAN Transformer
VFD Variable Frequency Drive
POWER

Table of Contents