APPENDIX B 09FC FREE COOLING MODULE CONTROLLER (CONT)
Alarms
Navigation: i-Vu
®
/ Field Assistant: Properties > Control Program
> Alarms
I/O Points
Navigation: i-Vu
®
/ Field Assistant: Properties > Control Program
> I/O Points
Point Name – Description Range
Equipment Alarm – Indicates if the unit is in a general equipment alarm. R: Normal/Alarm
Leaving Water Temperature – Indicates if the leaving water temperature exceeds the high or low alarm
limits.
R: Normal/Alarm
Entering Water Temperature – Indicates if the entering water temperature exceeds the high or low alarm
limits.
R: Normal/Alarm
Outdoor Air Temperature – Indicates if the outdoor air temperature exceeds the high or low alarm limits. R: Normal/Alarm
Leaving Water Temp Sensor – Indicates if the leaving water temperature sensor fails. R: Normal/Alarm
Entering Water Temp Sensor – Indicates if the entering water temperature sensor fails. R: Normal/Alarm
Outdoor Air Temp Sensor – Indicates if the outdoor air temperature sensor fails. R: Normal/Alarm
Fan VFD Fail Alarm – Indicates if the fan variable frequency drive is commanded On while its running status
is Off.
R: Normal/Alarm
Lvg Water Temp Hi Alarm – Indicates if the leaving water temperature exceeds the outdoor air temperature. R: Normal/Alarm
Negative DeltaT Alarm – Indicates if the leaving water temperature exceeds the entering water temperature. R: Normal/Alarm
WARNING
Do not change the Value, Offset/Polarity, Exp:Num, I/O
Type, Sensor/Actuator Type, Min/Max, or Resolution I/O
configuration parameter for the points listed below. Changing
these parameters could cause improper control and/or equip-
ment damage.
Use extreme caution if locking a point as this may also cause
improper control and/or equipment damage.
Point Name – Description Range
Remote Contact – The remote contact input's current state. R: Open/Close
OAT Sensor – The value of the controller's outdoor air temperature sensor input, prior to any operator-
configured Calibration Offset.
R: -56 to 245°F
Leaving Water Temp – The value of the controller’s leaving water temperature sensor input, prior to any
operator-configured Calibration Offset.
R: -56 to 245°F
Entering Water Temp – The value of the controller’s entering water temperature sensor input, prior to any
operator-configured Calibration Offset.
R: -56 to 245°F
Fan VFD Run Status – The fan VFD status input's current state. R: Off/On
Ext Demand Limit – The external demand limit input's current state. R: Off/On
Fan VFD Speed – The assigned output channel's current commanded, configuration dependent, fan VFD
speed output.
R: 0 to 100%
Bypass Valve – The assigned output channel's current commanded, configuration dependent, bypass valve
analog output.
R: 0 to 100%
Valve Command The assigned output channel's current commanded, configuration dependent, valve floating
motor binary outputs.
R: Close/Open
Alarm Lamp – The assigned output channel's current commanded, configuration dependent, alarm output. R: Off/On
Fan VFD Enable – The assigned output channel's current commanded, configuration dependent, fan VFD
enable output.
R: Off/On